2. Classic Slave

• Classic Slave is the designation of the second FX in a two-inverter, split-phase system that produces

240 VAC without using an FW-X240 Auto Transformer.

• This FX is plugged into Port 02 of the HUB.

OB Slave L1 and OB Slave L2 designations are used in OutBack Parallel Stacking or OutBack Series/

Parallel stacking

3. OB Slave L1

• In an OutBack Parallel single-phase system, all the Slave FXs on a single 120 VAC leg are designated

OB Slave L1.

• In an OutBack Series split-phase system, which will include an FW-X240 or PSX-240 Auto Transformer,

any FX that runs in parallel to the Master FX is designated OB Slave L1. These FXs must be plugged
into the lowest HUB Ports.

• The OB Slave L1 Stacking is typically used for an entirely off -grid application such as a cabin that

does not require 240 volts.

4. OB Slave L2

• In an OutBack Series split-phase system, any Slave FX that runs in series with the Master FX is

designated OB Slave L2.

5. 3ph Master

• In 3-phase stacking, the Master FX is designated as 3ph Master.

3ph Master and 3ph Slave designation are used in OutBack 3-phase stacking.

6. 3ph Slave

• I n 3 - p h a s e s t a c k i n g, e a c h o f t h e S l ave F X s, w h i c h s h o u l d b e p l u g g e d i n to H U B

Po r t s 0 2 ( p h a s e B ) a n d 0 3 ( p h a s e C ) re s p e c t i ve l y, i s d e s i gn a te d a s 3 p h S l ave.

• W h e n t h e H U B j u m p e r i s s e t b e t we e n Po r t 0 2 a n d Po r t 0 3 , t h e H U B i d e n t i f i e s a

p h a s e fo r e a c h S l ave F X .

Stacking Phases/Assigning FX Status (in order):

1. 1-2ph Master*

2. Classic Slave

3. OB Slave L1

4. OB Slave L-2

5. 3ph Master

6. 3ph Slave

*GTVX and GVFX models show “Master” on the screen