34

The default value for the power save level slave

adjust only screen is 1. Press or to

adjust this value. Press to change the

value of each Slave FX.

The Slave(s) must be connected to Port 2 or

higher on the HUB.

With the Master FX default value of zero in the

power save level master adjust only screen, all of

the Slave FX’s will remain OFF until the Master

FX needs help and calls for the Slave FX’s with

a Slave ranking equal to 1 to come ON.

Choose a diff erent Slave ranking for each Slave

FX. This helps assure proper operation and allows

them to come ON one at a time saving power in

the long run. Otherwise, with a default value of 1

for all Slaves, they will all come on whenever a 12

amp load calls for more power, but then can

quickly shut off because multiple FXs provide far

more than the required 12 amps. Ranking them

1, 2, 3, 4 etc. means they will come on one at time

as needed to better serve the loads and conserve

energy.

ADV/FX/STACK-----------P02

power save level 1

slave adjust only

DOWN INC DEC PORT

ADV/FX/STACK-----------------

stacking setup

completed

TOP ADV MAIN

Press to return to the Main Menu.

Press to view the fi nal stacking screen.

INC

DEC

DOWN

MAIN

PORT