OutBack Parallel Stacking

• Four FXs in a single system are referred to as a Quad Stack.

• The FX installed at the bottom of the stack is plugged into Port 1 of the HUB.

• The second, third, and fourth FXs are plugged into Ports 2, 3, and 4 respectively

.

PRESS UNTIL 141,

THEN PRESS ENTER.

At completion, each Slave FX in Ports 2, 3, and 4 will be in parallel with the Master in Port 01. Addi-

tional Slaves can also be programmed as OB Slave L1 following the instructions above. All the Slave FXs

connected to Ports 2, 3, and 4 are now in parallel with the Master in Port 01. Remain in this screen. The

next step is to rank the Slaves in relation to the Master.

ADV/PASSWORD--------------

enter the password

132

ENTER INC DEC EXIT

ADV/SETTINGS/WARNING

changes made could adversely
aff ect system performance

MAIN---------------------------

8:25:04A

SUM STATUS SETUP ADV

ADV/FX/PG2-------------------

choose category:

PG1 GRID GEN PG3

ADV/FX/PAGE 1---------------

choose category:

ADV INV CHGR PG2

ADV----------------------------

choose a device:

FX CC DC MATE

ADV/FX/STACK ----------P02

stack 1-2ph Master

phase

DOWN INC DEC PORT

ADV/FX/STACK---------P01

stack 1-2ph Master

phase

DOWN INC DEC PORT

ADV/FX/PAGE3---------------

choose category:

PG2 AUX STACK PG4

ADV/FX/STACK----------P04

stack OB Slave L1

phase

DOWN INC DEC PORT

ADV/FX/STACK----------P03

stack OB Slave L1

phase

DOWN INC DEC PORT

Push the soft key until
Port 01 appears.

Press the soft key until
Port 02 appears. Press the
soft key twice until the stack phase
ob slave L1
screen appears.

Press the soft key until
Port 03 appears. Press the
soft key twice until the stack phase
ob slave L1
screen appears.

Press the soft key until
Port 04 appears. Press the
soft key twice until the “stack
phase ob slave L1” screen.