beautypg.com

Outback Power Systems VFX Series Programming Manual User Manual

Page 12

background image

11

ADV/FX/INVERTER-------P00

search

60 cycles

pulse spacing

DOWN INC DEC PORT

ADV/FX/INVERTER-------P00

low battery 10.5 vdc
cut-out set point

DOWN INC DEC PORT

ADV/FX/INVERTER-------P00

low battery 12.5 vdc
cut-in set point

DOWN INC DEC PORT

ADV/FX/INVERTER-------P00

adjust 120 vac
output voltage

DOWN INC DEC PORT

The search pulse spacing screen adjusts the

amount of time the FX waits before producing

additional AC pulses to sense a load. The higher

the number of cycles, the lower the FX power

consumption, but the longer it takes before AC

loads are powered. The cycles range from 4 to

120 cycles (two seconds). Press to view

the low battery cut-out screen.

low battery cut-out establishes when the FX turns

off to avoid draining the battery. If an AC source

is available and AC INPUT is set to DROP, the FX

will transfer the AC loads on the FX to the AC

source. A built-in fi ve-minute delay reduces

nuisance FX shutdowns. This setting’s range is

between 9.0VDC and 12.0VDC. Press

to view the next INVERTER screen.

The low battery cut-in set point determines when

the FX will turn on after shutting off due to a low

battery voltage. A 10-minute fi xed delay reduces

on and off system cycling. This setting’s range is

between 10.0 VDC and 14.0 VDC. Press

to view the adjust output voltage screen.

A user can adjust the output voltage using this

screen. Adjustments might be necessary if some

loads are far away from the FX or if some are

sensitive to higher voltages. This setting’s range

is between 110VAC and 125VAC. Press

to view the next INVERTER screen.