Power requirements – HP StorageWorks 500 G2 Modular Smart Array User Manual

Page 34

background image

34

HP StorageWorks MSA500 G2 Storage System User Guide

CAUTION: To reduce the risk of damage to the equipment

when installing third-party options:

Do not permit optional equipment to impede airflow around the

storage system or to increase the internal rack temperature beyond
the maximum allowable limits.

Do not exceed the manufacturer’s TMRA.

Power requirements

Installation of this equipment must comply with local and regional electrical
regulations governing the installation of information technology equipment by
licensed electricians. This equipment is designed to operate in installations
covered by NFPA 70, 1999 Edition (National Electric Code) and NFPA-75, 1992
(code for Protection of Electronic Computer/Data Processing Equipment). For
electrical power ratings on options, refer to the product rating label or the user
documentation supplied with that option.

WARNING: To reduce the risk of personal injury, fire, or

damage to the equipment, do not overload the AC supply branch
circuit that provides power to the rack. Consult the electrical
authority having jurisdiction over wiring and installation
requirements of your facility.

CAUTION: Protect the storage system from power fluctuations

and temporary interruptions with a regulating UPS. This device protects
the hardware from damage caused by power surges and voltage spikes
and keeps the storage system in operation during a power failure.

When installing more than one storage system, you may need to use additional
power distribution devices to safely provide power to all devices. Observe the
following guidelines:

• Balance the storage system power load between available AC supply branch

circuits.

• Do not allow the overall system AC current load to exceed 80 percent of the

branch circuit AC current rating.

• Do not use common power outlet strips for this equipment.