Installing the Server in a Rack

Temperature Requirements

To be sure of continued safe and reliable operation of the equipment, install the
system in a well-ventilated, climate-controlled environment.

The Maximum Recommended Ambient Operating Temperature (TMRA) for most
server products is 35°C (95°F). The temperature in the room where the rack is
located should not exceed 35°C (95°F).

The operating temperature inside the rack will always be higher than the room
temperature and is dependent on the configuration of equipment in the rack. The
TMRA for each piece of equipment should be checked before installation. The
maximum internal rack temperature for your configuration should not exceed the
values shown in Table 2-1.

Table 2-1: Rack Internal Temperature Maximums

Equipment Included

Maximum Internal Rack

Temperature

Rack-mountable ProLiant
DL760 G2 servers

35°C (95°F)

HP rack-mountable options

35°C (95°F)

Other manufacturers’ options

Refer to other manufacturers’

specifications

CAUTION: To reduce the risk of damage to the equipment when installing
third-party options:

Be sure that the optional equipment does not impede airflow to the
rack-mountable ProLiant DL760 G2 servers or increase the internal rack
temperature beyond the HP specified maximum rating.

Be sure that the manufacturer’s TMRA of the optional equipment is not
exceeded when the equipment is installed in the rack.