NORD Drivesystems BU0510 User Manual
Page 40
POSICON position control for NORD frequency inverters, SK 530E and above
40
Subject to technical alterations
BU 0510 GB-3911
Parameter
{factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P405
Analog input 2 function
(Analog input 2 function)
up to SK
535E
P
0 ... 82
{ 0 }
This parameter is identical to P400.
P418
Analog output 1 function
(Analog output 1 function)
up to SK
535E
P
0 ... 52
{ 0 }
Analog functions (max. load: 5mA analog, 20mA digital):
An analog voltage (0 ... +10 Volt) can be taken from the control terminals (max. 5mA). Various
functions are available, whereby:
0 Volt analog voltage always corresponds to 0% of the selected value.
10 V always corresponds to the motor nominal values (unless otherwise stated) multiplied by the
P419 standardisation factor, e.g.:
100%
P419
value
nominal
Motor
10Volt
The possible functions are listed in the following tables.
P418
[-01]
...
[-03]
Analog output func.
(Analog output function)
SK 540E and
above
P
0 ... 52
{ all 0 }
[-01] = Analog output: analog output integrated into the FI
[-02] = First IOE, "External analog output of first IOE": Analog output 1 of thefirst IO
extension (SK xU4-IOE)
[-03] = Second IOE, "External analog output of second IOE": Analog output of thesecond IO
extension (SK xU4-IOE)
Analog functions (max. load: 5mA analog, 20mA digital):
An analog voltage (0 ... +10 Volt) can be taken from the control terminals (max. 5mA). Various
functions are available, whereby:
0 Volt analog voltage always corresponds to 0% of the selected value.
10 V always corresponds to the motor nominal values (unless otherwise stated) multiplied by the
P419 standardisation factor, e.g.:
100%
P419
value
nominal
Motor
10Volt
The possible functions are listed in the following tables.
List of possible analog functions for the analog outputs P418
(only POSICON functions)
Value Function
Description
29
Actual position
Within the limits of P615 and P616 the analog output indicates the actual position.