beautypg.com

NORD Drivesystems BU0280 User Manual

Page 71

background image

7 DeviceNet data transmission

BU 0280 GB

Subject to technical amendments

71

PZD3:

“Bus function Actual value 2"

(SK 200E: (P543[02]) or SK 500E (P544)) and

PZD4:

“Bus function Actual value 3"

(SK 200E: (P543[03]) or SK 500E (P545))



7.2.4

The status machine

The frequency inverter passes through a status machine“. The changes between various states are
triggered by the respective control commands in the process data control word. The actual status is returned
in the process data status word.
After switching on, the frequency inverter is in Switch-on disabled

status. This status can only be ended by

transmitting the

“ Shut down (Off 1)” command.

The answer to a master telegram normally does not yet contain a reaction to the control command. The
controller has to check the answers from the slaves as to whether the control command has been carried
out.

The following bits indicate the status of the frequency inverter:

Status

Bit 6

Switch-on

disable

Bit 5

Emergency

stop

Bit 4

Disable

voltage

Bit 3

Fault

Bit 2

Operation

enabled

Bit 1

Standby

Bit 0

Ready for

switch-on

Not

on

standby 0 X X 0 0 0 0

Switch-on

disabled

1 X X 0 0 0 0

Ready

for

switch-on

0 1 1 0 0 0 1

Activated

0 1 1 0 0 1 1

Operation

enabled 0 1 1 0 1 1 1

Error

0 X X 1 0 0 0

Error

active

0 X X 1 1 1 1

Emergency

stop

active

0 0 1 0 1 1 1