5 Parameterisation
BU 0280 GB
Subject to technical amendments
51
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P515
...
[-01]
…
...
[-03]
CAN address (system bus)
S
0 ... 255 dec
{ all 32 dec}
or { all 20 hex}
Setting of the system bus address.
… [-01] = Receive address for system bus
… [-02] = Broadcast – Receive address for system bus (slave)
… [-02] = Broadcast – Transmit address for system bus (master)
NOTE:
If up to four SK 200E are to be linked via the system bus, the addresses must be set as follows
FI 1 = 32, FI 2 = 34, FI 3 = 36, FI 4 = 38.
The system bus addresses should be set via the DIP switches 1/2 (Section 2.2.3).
P543
…
[-01]
...
…
[-03]
Actual bus value 1… 3
S
P
0 ... 22
{ [-01] = 01 }
{ [-02] = 04 }
{ [-03] = 09 }
The return value can be selected for bus actuation in this parameter.
NOTE:
For further details, please refer to the description for P418.
… [-01] = Actual bus value 1
… [-02] = Actual bus value 2
(only for PPO Type 2 or 4)
… [-03] = Actual bus value 3
(only for PPO Type 2 or 4)
Possible values which can be set:
0 =
Off
1 =
Actual frequency
2 =
Actual speed
3 =
Current
4 =
Torque current (100% = P112)
5 =
State of digital inputs and outputs
2
6 =
... 7 Reserved
8 =
Setpoint frequency
9 =
Error number
10 =
... 11 Reserved
12 =
Bus Out bits 0...7
13 =
... 16 Reserved
17 =
Value analog input 1 (P400)
18 =
Value analog input 2 (P405)
19 =
Setpoint frequency master value (P503)
20 =
Setpoint frequency after master value ramp
21 =
Actual frequency without master value slip
22 =
Speed from encoder
2
The assignment of the dig. inputs for P543 = 5
Bit 0 = DigIn 1
Bit 1 = DigIn 2
Bit 2 = DigIn 3
Bit 3 = DigIn 4
Bit 4 = DigIn 5
Bit 5 = DigIn 6
Bit 6 = DigIn 7
Bit 7 = Reserved
Bit 8 = Reserved
Bit 9 = Reserved
Bit 10 = Reserved
Bit 11 = Reserved
Bit 12 = Out 1
Bit 13 = Out 2
Bit 14 = Out 3
Bit 15 = Out 4