2 error messages 6.2.1 – NORD Drivesystems BU0280 User Manual
Page 64
Supplementary Manual DeviceNet for NORDAC SK 200E
64
Subject to technical amendments
BU 0280 GB
6.2 Error messages
6.2.1
Table of possible error messages (caused by the bus) in the frequency inverter
The following error messages concern bus-related messages which are indicated on the frequency inverter. A
complete list of error messages for the frequency inverter (SK 200E) can be found in the relevant manual
(BU0200).
Display in the
SimpleBox
Fault
Text in the ParameterBox
Cause
Remedy
Group
Details in
P700 / P701
E010
10.2
External bus module
telegram timeout
(Timeout of DeviceNet Bus
Watchdog)
Telegram transfer is faulty.
Check external connection.
Check bus protocol program process.
Check Bus master.
10.3
Timeout via (P151)
Telegram transfer is faulty.
Check watchdog time (P151)
Check external connection.
Check bus protocol program process.
Check Bus master.
Control word is invalid (Bit 10 = 0)
10.9
Module not found
The module entered in parameter (P120) is not available.