Supplementary Manual DeviceNet for NORDAC SK 200E

38

Subject to technical amendments

BU 0280 GB

4.2.3

Explanation of the I/O Assembly Data for the AC Drive Profile

Instance

Byte

Bit7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

20 0

Fault

Reset

Run

Fwd

1

2

Speed setpoint (Low byte)

3

Speed setpoint (High byte)

21 0

NetRef

NetCtrl

Fault

Reset

Run Rev

Run Fwd

1

2

Speed setpoint (Low byte)

3

Speed setpoint (High byte)

70 0

Running1

Faulted

1

2

Actual speed (Low byte)

3

Actual speed (High byte)

71 0

At Ref

Ref From
Net

Ctrl From
Net

Ready

Running2
(Rev)

Running1
(Fwd)

Warning

Faulted

1

Drive State ( explanation in Class 41 Attribute 6)

2

Actual speed (Low byte)

3

Actual speed (High byte)

4.2.3.1 Description of the bits in the control and status word

Run Forward
High level = The FI is switched on and the motor accelerates to its setpoint
Low level = The motor is braked on the set ramp to 0 rpm and the FI switched off

Run Reverse
As for “Run Forward” but with the opposite direction of rotation.

Fault Reset
A Low – High flank resets an error in the FI

NetCtrl
With a High level, the control words sent via the DeviceNet bus are valid The settings P509 and P510 in the FI
are not affected

NetRef
With a High level, the setpoint words sent via the DeviceNet bus are valid The settings P509 and P510 in the
FI are not affected

Fault
High level indicates an error in the FI

Warning
High level indicates a warning in the FI. See Bit 7 in the USS status word

Run 1
FI has a clockwise rotating field

Run 2
FI has an anticlockwise rotating field

Ready
FI is switched on, i.e. voltage is applied to the motor

Ctrl From Net
The FI is controlled via DeviceNet. Only the status of “NetCtrl” is imaged in the control word. The parameters
P509 & P510 are not queried.