7 DeviceNet data transmission

BU 0280 GB

Subject to technical amendments

67

7.2 NORDAC profile

7.2.1

Control word (STW)

The control word (STW) is the first word transferred to the frequency inverter in the process data section in
an order telegram.

PZD1 PZD2 PZD3 PZD4

STW SW1 SW2/3

SW2/3

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0


Meaning of the individual bits:

Bit

Value

Significance

Comments

0

0

OFF 1

Return with the brake ramp, at f=0Hz voltage activation

1 ON

Standby

1 0 OFF

2

Disable voltage; the inverter output voltage is switched off; the FI goes into
switch-on disabled status.

1

Operating condition

OFF 2 is cancelled

2 0 OFF

3

Emergency stop with programmed emergency stop time; at f = 0Hz voltage
enable; the FI goes into switch-on disabled status

1

Operating condition

OFF 3 is cancelled

3 0 Disable

operation Disable voltage; the inverter output voltage is switched off; the FI goes into

standby status.

1

Enable operation

Output voltage enabled, run-up to present setpoint.

4 0 Disable

run-up

encoder

Run-up encoder is set to zero; at f = 0Hz no voltage enable; FI remains in
operation enabled status.

1

Operating condition

Run-up encoder is enabled

5

0

Stop run-up encoder

Freezing of actual setpoint from run-up encoder (hold frequency).

1

Enable run-up encoder Enable setpoint on run-up encoder

6

0

Disable setpoint

Selected setpoint is set to zero in the run-up encoder.

1

Enable setpoint

Selected setpoint on run-up encoder is activated.

7 0 No

acknowledgement

With the switch from 0 to 1, errors which are no longer active are
acknowledged.

1 Acknowledge

Note: If a digital input is programmed to the function "Error ack.", this bit must
not be set permanently to 1 via the bus (otherwise this will prevent flank
detection).

8 0

1

Bit 8 active

Bus bit 8 from the control word is set. (only for SK 200E and SK 500E)
For further details of function, please refer to parameter (P481).

9 0

1

Bit 9 active

Bus bit 9 from the control word is set. (only for SK 200E and SK 500E)
For further details of function, please refer to parameter (P481).

10

0

PZD invalid

The transmitted process data is invalid.

1

PZD valid

Valid process data is transferred from the master.
Note:

If only setpoints are transferred via the bus, this bit must be set so that

the transferred setpoint is valid.

11 0

1

Rotation right

Rotation right (priority) is on.

12 0

1

Rotation left

Rotation left is on.

13 0/1

Reserved

14 0/1 Parameter set switch

Bit 0

00 = Parameter set 1
01 = Parameter set 2

10 = Parameter set 3
11 = Parameter set 4

15 0/1 Parameter set switch

Bit 1