2 nordac profile 7.2.1 – NORD Drivesystems BU0280 User Manual
Page 67
7 DeviceNet data transmission
BU 0280 GB
Subject to technical amendments
67
7.2 NORDAC profile
7.2.1
Control word (STW)
The control word (STW) is the first word transferred to the frequency inverter in the process data section in
an order telegram.
PZD1 PZD2 PZD3 PZD4
STW SW1 SW2/3
SW2/3
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Meaning of the individual bits:
Bit
Value
Significance
Comments
0
0
OFF 1
Return with the brake ramp, at f=0Hz voltage activation
1 ON
Standby
1 0 OFF
2
Disable voltage; the inverter output voltage is switched off; the FI goes into
switch-on disabled status.
1
Operating condition
OFF 2 is cancelled
2 0 OFF
3
Emergency stop with programmed emergency stop time; at f = 0Hz voltage
enable; the FI goes into switch-on disabled status
1
Operating condition
OFF 3 is cancelled
3 0 Disable
operation Disable voltage; the inverter output voltage is switched off; the FI goes into
standby status.
1
Enable operation
Output voltage enabled, run-up to present setpoint.
4 0 Disable
run-up
encoder
Run-up encoder is set to zero; at f = 0Hz no voltage enable; FI remains in
operation enabled status.
1
Operating condition
Run-up encoder is enabled
5
0
Stop run-up encoder
Freezing of actual setpoint from run-up encoder (hold frequency).
1
Enable run-up encoder Enable setpoint on run-up encoder
6
0
Disable setpoint
Selected setpoint is set to zero in the run-up encoder.
1
Enable setpoint
Selected setpoint on run-up encoder is activated.
7 0 No
acknowledgement
With the switch from 0 to 1, errors which are no longer active are
acknowledged.
1 Acknowledge
Note: If a digital input is programmed to the function "Error ack.", this bit must
not be set permanently to 1 via the bus (otherwise this will prevent flank
detection).
8 0
1
Bit 8 active
Bus bit 8 from the control word is set. (only for SK 200E and SK 500E)
For further details of function, please refer to parameter (P481).
9 0
1
Bit 9 active
Bus bit 9 from the control word is set. (only for SK 200E and SK 500E)
For further details of function, please refer to parameter (P481).
10
0
PZD invalid
The transmitted process data is invalid.
1
PZD valid
Valid process data is transferred from the master.
Note:
If only setpoints are transferred via the bus, this bit must be set so that
the transferred setpoint is valid.
11 0
1
Rotation right
Rotation right (priority) is on.
12 0
1
Rotation left
Rotation left is on.
13 0/1
Reserved
14 0/1 Parameter set switch
Bit 0
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
15 0/1 Parameter set switch
Bit 1