NORD Drivesystems BU0280 User Manual
Page 27
![background image](/manuals/372713/27/background.png)
2 Assembly and installation
BU 0280 GB
Subject to technical amendments
27
Configuration example
A DeviceNet subscriber SK TU4-DEV is connected to an SK 200E series frequency inverter via a BUS
connection unit SK TI4-TU-BUS. The field bus address (DeviceNet address) should be “14” and a baud rate of
250kBaud should be selected. The system bus only includes the frequency inverter and the DeviceNet
module. The termination resistor for the system bus is to be set at the frequency inverter. The DIP switches on
the DeviceNet module must be set as follows:
Range
Significance
DIP-Switch
ON - OFF
Configuration
example
Address
ing
Address-Bit 5
2
5
0
Address-Bit 4
2
4
0
Address-Bit 3
2
3
8
Address-Bit 2
2
2
4
Address-Bit 1
2
1
2
Address-Bit 0
2
0
0
Example address:
14
Baud
rate
Baud rate Bit 1
2
1
0
Baud rate Bit 0
2
0
1
Baud rate
1 = 250kBaud
BUS
termination
No significance
Always OFF
No significance
Always OFF
System bus
-
OFF