NORD Drivesystems BU0280 User Manual
Page 23

2 Assembly and installation
BU 0280 GB
Subject to technical amendments
23
2.2.2.2 Control connections for SK TU4-DEV(-…)
The double spring-loaded terminal bar of the technology unit is colour coded, and therefore indicates the three
different potential levels.
A separate voltage source can be used to supply the DOs. However, by bridging the 24V o and GND o to one
of the terminals of the system bus level 24V and GND it is possible to implement the supply of the DOs.
Connection of up to 4 sensors and 2 actuators is made via the terminal bar. Alternatively, the
SK TU4-DEV-M12 module enables the connection of these I/Os via the M12 round plug connector (5 pin
socket, A-coded) mounted on the front.
Field bus level
DeviceNet
System bus level and digital inputs
Digital outputs
24V
BUS
DVN +
IN
DVN -
IN
GND
BUS
SHLD
24V
24V
(as for 11)
GND
GND
DIN 1
GND
24V
(as for 11)
DIN 2
DIN 4
24V
(as for 11)
24V
O
DO
DO 1
GND
O
DO
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
24V
BUS
DVN +
OUT
DVN -
OUT
GND
BUS
PE
24V
(as for 11)
Sys +
Sys -
GND
DIN 3
GND
24V
(as for 11)
DIN 4
GND
24V
(as for 11)
GND
O
DO
DO 2
GND
O
DO
Connection example: SK TU4-DEV to SK 200E
SK205E… - connection unit (SK TI4...)
SK TU4-CAO… - connection unit (SK TI4-TU-BUS)
Voltage
source
24V DC
DeviceNet
participant
X-1
Voltage
source
24V DC
DeviceNet
participant
X+1