NORD Drivesystems BU0280 User Manual
Page 53
5 Parameterisation
BU 0280 GB
Subject to technical amendments
53
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P552
…
[-01]
…
[-02]
System bus master cycle time
S
0 / 0.1
… 100.0 ms
{ 0 }
In this parameter, the cycle time for the system bus master mode and the CAN open encoder is
set (see P503/514/515):
… [-01] =
Cycle time for system bus master functions
… [02] = Cycle time for system bus absolute value encoder
With the setting 0 “Auto” the default value (see table) is used.
According to the baud rate set, there are different minimum values for the actual cycle time:
Baud rate
Minimum value t
Z
System bus master
default
System bus absolute
default
10kBaud
10ms
50ms
20ms
20kBaud
10ms
25ms
20ms
50kBaud
5ms
10ms
10ms
100kBaud
2ms
5ms
5ms
125kBaud 2ms
5ms
5ms
250kBaud 1ms
5ms
2ms
500kBaud 1ms
5ms
2ms
1000kBaud 1ms
5ms
2ms
P560
Save in EEPROM
S
0 ... 1
{ 1 }
0 =
Changes to the parameter settings are no longer saved on the EEPROM. Previously
saved settings remain stored, even if the FI is disconnected from the mains; however
new changes are not saved after a mains failure.
1 =
All parameter changes are automatically written to the EEPROM and remain stored there
even if the FI is disconnected from the mains supply.
NOTE:
If BUS communication is used to implement parameter changes, it must be
ensured that the maximum number of write cycles (100,000 x) in the EEPROM is
not exceeded.