Supplementary Manual DeviceNet for NORDAC SK 200E

50

Subject to technical amendments

BU 0280 GB

5.1.3

Supplementary parameter (P500)

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P509

Control word source

S

0 ... 4

{ 0 }

Selection of the interface via which the FI is controlled.

0 = Control terminals or keyboard control

** with the SimpleBox (if (P510)=0), the

ParameterBox or via BUS I/O Bits.

1 = Only control terminals

*, the FI can only be controlled via the digital and analog input

signals or via the Bus I/O Bits.

2 = USS control word *,

the control signals (enable, rotation direction, etc.) are transferred

via the RS485 interface, the setpoint via the analog input or the fixed frequencies.

3 = System bus

* ( control via DeviceNet )

4 = System bus broadcast

*) Keyboard control (SimpleBox, ParameterBox, PotentiometerBox) is disabled,

parameterisation is still possible.

**) If the communication during keyboard control is interrupted (time out 0.5 sec), the

FI will disable without an error message.

NOTE:

As an alternative to setting the parameter, System Bus Broadcast can be selected with DIP
switch 3.

P510

... [-01]

... [-02]

Setpoint source

S

0 ... 4

{ [-01] = 0 }

{ [-02] = 0 }

Selection of the setpoint source to be parameterised.

[-01] = Main setpoint source

[-02] = Subsidiary setpoint source

Selection of the interface via which the FI receives the setpoint.

0 = Auto:

The source of the auxiliary setpoint is

automatically derived from the setting in the
parameter P509 >Interface<

1 = Control terminals

, digital and analog inputs control

the frequency, including fixed frequencies

2 = USS

3 = System bus

4 = System bus broadcast

P513 Telegram

downtime

S

-0.1 / 0.0 /
0.1 ... 100.0 s

{ 0.0 }

Monitoring function of the active bus interface. Following receipt of a valid telegram, the next
one must arrive within the set period. Otherwise the FI reports an error and switches off with the
error message E010 >Bus Time Out<.

0.0 = Off

: Monitoring is switched off.

-0.1 = no error

: Even if communication between BusBox and FI is interrupted (e.g. 24V error,

Box removed, etc.), the FI will continue to operate unchanged.

P514

CAN baud rate (system bus)

S

0 ... 7

{ 5 }

Setting of the transfer rate (transfer speed) via the system bus interface. All bus subscribers
must have the same baud rate setting.

0 =

10kBaud

1 =

20kBaud

2 =

50kBaud

3 =

100kBaud

4 =

125kBaud

5 =

250kBaud

6 =

500kBaud

7 =

1Mbaud *

*) Safe operation cannot be guaranteed