2.1.2

Installation of the Customer Unit SK CU4-DEV

WARNING

Installation must be carried out by qualified personnel only, paying particular attention to
safety and warning instructions.

Modules must not be inserted or removed unless the device is free of voltage. The slots
may only be used for the applicable modules.

Installation of the SK CU4... customer unit remote from the frequency inverter is not
permitted. This must be installed in the immediate vicinity of the SK 200E frequency
inverter.

The installation of customer units is carried out in the connection unit SK T14

… SK 200E underneath the

control terminal bar. Fastening is by means of the terminal bar of the frequency inverter and two M4x20 screws
(bag enclosed with the customer unit). Only one customer unit per FI is possible!
The pre-assembled cables for connection to the frequency inverter (SK 200E) are also included in the bag
enclosed with the customer unit. Connections are made according to the following table:

SK TI4-

with integrated customer unit SK CU4-DEV

Internal customer unit SK CU4-DEV

Bag enclosed with internal customer unit


Function

Terminal label

Cable colour

Power supply

(between frequency inverter and customer unit)

44

24V brown

40

GND blue

System bus

77

SYS+ black

78

SYS- grey


NOTE

Set the termination resistors of the system bus!

See Section 2.2.3 “Configuration”