beautypg.com

NORD Drivesystems BU0280 User Manual

Page 30

background image

Supplementary Manual DeviceNet for NORDAC SK 200E

30

Subject to technical amendments

BU 0280 GB

3.1.2

Signal status LEDs

This manual only describes the LED signal statuses of the DeviceNet modules. Information for the frequency
inverter LEDs (SK 200E) can be found in the relevant manual (BU0200).

3.1.2.1 Module-specific displays

The status of the technology unit or the system bus is indicated by the LEDs DS and DE.

LED (green)

DS

Device State

LED (red)

DE

Device Error

Significance

... ... Slow flashing = 2Hz (0.5s cycle)

… Rapid flashing= 4Hz (0.25s cycle)

OFF

OFF

Technology unit not ready, no control voltage

ON

OFF

Technology unit ready, no error, at least one frequency inverter is
communicating via the system bus

ON

Flashing 0.25s

Technology unit ready, however

one or more of the connected frequency inverters has a fault status

(see frequency inverter manual)

Flashing 0.5s

OFF

Technology unit ready and at least one further subscriber is connected
to the system bus, but

No frequency inverter on the system bus (or connection interrupted)

Address error for one or more system bus subscribers

Flashing 0.5s

Flashing 0.25s

Flash interval

1 x - 1s pause

System bus is in status "Bus Warning"

Communication on system bus interrupted or

No other subscriber present on the system bus

Flashing 0.5s

Flashing 0.25s

Flash interval

2 x - 1s pause

System bus is in status "Bus off" or

The system bus 24V power supply was interrupted during operation

Flashing 0.5s

Flashing 0.25s

Flash interval

3 x - 1s pause

No system bus 24V power supply

(system bus is in status "Bus off")

Flashing 0.5s

Flashing 0.25s

Flash interval

4 x - 1s pause

technology unit error present

Details: under parameter P170 or P173

OFF

Flashing 0.25s

Flash interval

1

7 - 1s pause

System error, internal program sequence interrupted

EMC interference (observe wiring guidelines!)

Module faulty