beautypg.com

Meter location, orientation and applications, Remote amplifier outdoor location, Pipelines and fluid flow – Badger Meter M-Series M2000 User Manual

Page 8

background image

METER LOCATION, ORIENTATION AND APPLICATIONS

The M2000 provides two amplifier mounting options: an integral or meter mount option and a junction box/remote option

Meter mount amplifier

Junction box with remote amplifier

Figure 5: Amplifier Mounting Options

Remote Amplifier Outdoor Location

The amplifier can be installed and operated outdoors However, it must be protected from the elements, as follows:

The ambient environment/temperature rating for the unit is –4…140° F (–20…60° C)

If an indoor location is within 500 feet (152 meters) of the detector, consider increasing the cable length and

mounting the amplifier indoors

At minimum, fabricate a roof or shield over and/or around the amplifier to protect the LCD display screen from direct

sunlight

Pipelines and Fluid Flow

Take the following precautions during installation:

Do not install the meter on pipes with extreme pipe vibrations If pipes are vibrating, secure the piping with

appropriate pipe supports in front of and behind the meter If vibrations cannot be restrained, mount the amplifier in

a remote location

Do not install the detector close to pipeline valves, fittings or impediments that can cause flow disturbances

For detectors with PTFE liners, do not install the detector on suction sides of pumps

Do not install the detector on outlet sides of piston or diaphragm pumps Pulsating flow can affect meter

performance

Avoid installing the detector near equipment that produces electrical interference such as electric motors, transformers,

variable frequency, and power cables

Verify that both ends of the signal cables are securely fastened

Place power cables and signal cables in separate conduits

Place the meter where there is enough access for installation and maintenance tasks

M-Series® M2000 Electromagnetic Flow Meter

Page 8

August 2012