Badger Meter M-Series M2000 User Manual
Page 40
Communication: Port Settings
Port Address
[1]
S
This parameter establishes the MODBUS RTU address MODBUS RTU requests will only be processed
if the configured port address of the meter matches the request address found in the MODBUS RTU
packet The range of addresses supported by MODBUS RTU is 1…247 MODBUS RTU request packets
with an address of 0 imply the packet is to be treated as a broadcast packet
To change the port address, follow these steps from the Port A Settings menu:
1 Select Port Address to view the Port Address display
2 Select the desired port address (1…247)
3 Press [E] to save the option and to return to the Port A Settings menu
External Port
Address
[1]
S
For PROFIBUS® use only This parameter allows configuration of the PROFIBUS DP daughterboard
address
Baud Rate
[9600]
S
The following Baud Rates are supported
• 9600
• 19200
• 38400
To change the baud rate, follow these steps from the Port A Settings menu:
1 Select Baud Rate to view the Baud Rate display
2 Select one of the following baud rates: 9600, 19200 or 38400
3 Press [E] to save the option and to return to the Port A Settings menu
Data Bits
[8 bits]
S
The Data Bits parameter configures the port data bits The following data bits are supported:
• 8 bits
• 7 bits
• 5 bits
To change the data bits, follow these steps from the Port A Settings menu:
1 Select Data Bits to view the Data Bits display
2 Select one of the following: 8 Bits, 7 Bits or 5 Bits
3 Press [E] to save the option and to return to the Port A Settings menu
M-Series® M2000 Electromagnetic Flow Meter
Page 40
August 2012