OPERATION

4

71

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

SP_RATE_UP

SP_RATE_UP

SP_RATE_UP

SP_RATE_UP

Setpoint Rate Up

Setpoint Rate Up

Setpoint Rate Up

Setpoint Rate Up

RW

Ramp rate at which upward setpoint changes are acted on in

"Auto" mode, in PV units per second. If the ramp rate is set to

zero or the block is in a mode other than "Auto", then the

setpoint will be used immediately.

+INF

Setting:

0.0...+INF

STATUS_OPTS

STATUS_OPTS

STATUS_OPTS

STATUS_OPTS

Status Options

Status Options

Status Options

Status Options

RW

Options which the user may select in the block processing of

status.

No option selected

Setting:

IFS if Bad IN: Set Initiate Fault State status in OUT if the
status of IN is "Bad".

IFS if Bad CAS_IN: Set Initiate Fault State status in OUT if the
status of CAS_IN is "Bad".

Use Uncertain as Good: If the status of IN is "Uncertain",
treat it as "Good" otherwise treat it as "Bad".

Target to Man if Bad IN: Set the target mode to "Man" if the
status of the IN parameter is "Bad". This latches a PID block
into the "Man" state of the input ever goes "Bad".

Target to next permitted mode if BAD CAS_IN

TRK_IN_D

TRK_IN_D

TRK_IN_D

TRK_IN_D

Tracking Input

Tracking Input

Tracking Input

Tracking Input

Discrete

Discrete

Discrete

Discrete

RW

This discrete input is used to initiate external tracking of the

block output to the value specified by TRL_VAL.

Status

RW

Status of TRK_IN_D

Value

RW

Value of TRK_IN_D

TRK_SCALE

TRK_SCALE

TRK_SCALE

TRK_SCALE

Tracking Scale

Tracking Scale

Tracking Scale

Tracking Scale

RW

The high and low scale values, engineering units code and

number of digits to the right of the decimal point associated

with TRK_VAL.

EU at 100%

RW

The engineering unit value which represents the upper end of

range of the associated block parameter.

100

EU at 0%

RW

The engineering unit value which represents the lower end of

range of the associated block parameter.

0

Units Index

RW

Device Description units code index for the engineering unit

descriptor for the associated block value.

Uninitialized

Setting:

All units are possible.

Decimal Point

RW

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the

specified parameter.

0

TRK_VALUE

TRK_VALUE

TRK_VALUE

TRK_VALUE

Tracking Value

Tracking Value

Tracking Value

Tracking Value

RW

This input is used as the track value when external tracking is

enabled by TRK_IN_D.

Status

RW

Status of TRK_VAL

Value

RW

Value of TRK_VAL

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

Update Event

Update Event

Update Event

Update Event

R

This alert is generated by any change to the static data.

Unacknowledged

R

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

Proportional Integral Derivative Block

Parameter
DD Name

Access

Description
settings

Initial Value