SP_RATE_UP
SP_RATE_UP
SP_RATE_UP
SP_RATE_UP
Setpoint Rate Up
Setpoint Rate Up
Setpoint Rate Up
Setpoint Rate Up
RW
Ramp rate at which upward setpoint changes are acted on in
"Auto" mode, in PV units per second. If the ramp rate is set to
zero or the block is in a mode other than "Auto", then the
setpoint will be used immediately.
+INF
Setting:
0.0...+INF
STATUS_OPTS
STATUS_OPTS
STATUS_OPTS
STATUS_OPTS
Status Options
Status Options
Status Options
Status Options
RW
Options which the user may select in the block processing of
status.
No option selected
Setting:
•
IFS if Bad IN: Set Initiate Fault State status in OUT if the
status of IN is "Bad".
•
IFS if Bad CAS_IN: Set Initiate Fault State status in OUT if the
status of CAS_IN is "Bad".
•
Use Uncertain as Good: If the status of IN is "Uncertain",
treat it as "Good" otherwise treat it as "Bad".
•
Target to Man if Bad IN: Set the target mode to "Man" if the
status of the IN parameter is "Bad". This latches a PID block
into the "Man" state of the input ever goes "Bad".
•
Target to next permitted mode if BAD CAS_IN
TRK_IN_D
TRK_IN_D
TRK_IN_D
TRK_IN_D
Tracking Input
Tracking Input
Tracking Input
Tracking Input
Discrete
Discrete
Discrete
Discrete
RW
This discrete input is used to initiate external tracking of the
block output to the value specified by TRL_VAL.
Status
RW
Status of TRK_IN_D
Value
RW
Value of TRK_IN_D
TRK_SCALE
TRK_SCALE
TRK_SCALE
TRK_SCALE
Tracking Scale
Tracking Scale
Tracking Scale
Tracking Scale
RW
The high and low scale values, engineering units code and
number of digits to the right of the decimal point associated
with TRK_VAL.
EU at 100%
RW
The engineering unit value which represents the upper end of
range of the associated block parameter.
100
EU at 0%
RW
The engineering unit value which represents the lower end of
range of the associated block parameter.
0
Units Index
RW
Device Description units code index for the engineering unit
descriptor for the associated block value.
Uninitialized
Setting:
All units are possible.
Decimal Point
RW
The number of digits to the right of the decimal point which
should be used by an interface device in displaying the
specified parameter.
0
TRK_VALUE
TRK_VALUE
TRK_VALUE
TRK_VALUE
Tracking Value
Tracking Value
Tracking Value
Tracking Value
RW
This input is used as the track value when external tracking is
enabled by TRK_IN_D.
Status
RW
Status of TRK_VAL
Value
RW
Value of TRK_VAL
UPDATE_EVT
UPDATE_EVT
UPDATE_EVT
UPDATE_EVT
Update Event
Update Event
Update Event
Update Event
R
This alert is generated by any change to the static data.
Unacknowledged
R
A discrete enumeration which is set to "Unacknowledged"
when an alarm occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
Uninitialized
Setting:
Uninitialized / Acknowledged / Unacknowledged
Proportional Integral Derivative Block
Parameter
DD Name
Access
Description
settings
Initial Value