Operation – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual
Page 16
4
OPERATION
16
H250 M40
www.krohne.com
02/2014 - 4001208201 - AD H250 M40 FF R02 en
DISABLED
Disabled
RW
The disabled state of each alarm.
Uninitialized
Setting:
•
Disc Alm Diabled
•
Block Alm Diabled
•
Fail Alm Diabled
•
Off Spec Alm Diabled
•
Maint Alm Diabled
•
Check Alm Diabled
BLOCK_ALM
BLOCK_ALM
BLOCK_ALM
BLOCK_ALM
Block Alarm
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the "Active" status in the "Status"
attribute. As soon as the "Unreported" status is cleared by the
alert reporting task, another block alert may be reported
without clearing the "Active" status, if the subcode has
changed.
UNACKNOWLEDGED
Unacknowledged
R/W
A discrete enumeration which is set to "Unacknowledged"
when an alarm occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
Uninitialized
Setting:
•
Uninitialized
•
Acknowledged
•
Unacknowledged
ALARM_STATE
Alarm State
R
A discrete enumeration which gives an indication of whether
the alert is active and whether it has been reported.
Uninitialized
Setting:
•
Uninitialized
•
Clear-Reported
•
Clear-Not Reported
•
Active-Reported
•
Active-Not Reported
TIME_STAMP
Time Stamp
R
The time when evaluation of the block was started and a
change in alarm/event state was detected that is unreported.
The time stamp value will be maintained constant until alert
confirmation has been received – even if another change of
state occurs.
Uninitialized
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
SUB_CODE
Subcode
R
An enumeration specifying the cause of the alert to be
reported.
Other
Setting:
•
Other
•
BlockConfiguration
•
LinkConfiguration
•
SimulationActive
•
LocalOverride
•
DeviceFaultState
•
DeviceMaintenance
•
InputFailure
•
Output failure
•
MemoryFailure
•
LostStaticData
•
LostNVData
•
RbackCheck
•
MaintenanceNeeded
•
PowerUp
•
OutOfService
VALUE
Value
R
The value of the associated parameter at the time the alert
was detected.
0
Setting:
0...255
Foundation Fieldbus parameters for Resource Block
Parameter
DD Name
Access
Description
Settings
Initial
AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 16 Friday, February 21, 2014 11:25 AM