Operation – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual
Page 32
4
OPERATION
32
H250 M40
www.krohne.com
02/2014 - 4001208201 - AD H250 M40 FF R02 en
SUB_CODE
Subcode
R
An enumeration specifying the cause of the alert to be reported.
Other
Setting:
•
Other
•
BlockConfiguration
•
LinkConfiguration
•
SimulationActive
•
LocalOverride
•
DeviceFaultState
•
DeviceMaintenance
•
InputFailure
•
OutputFailure
•
MemoryFailure
•
LostStaticData
•
LostNVData
•
RbackCheck
•
MaintenanceNeeded
•
PowerUp
•
OutOfService
VALUE
Value
R
The value of the associated parameter at the time the alert was
detected.
0
Setting:
0...255
UPDATE_EVT
UPDATE_EVT
UPDATE_EVT
UPDATE_EVT
Update Event
This alert is generated by any change to the static data.
UNACKNOWLEDG
ED
Unacknowledged
RW
A discrete enumeration which is set to "Unacknowledged" when
an alarm occurs, and set to "Acknowledged" by a write from a
human interface device or other entity which can acknowledge
that the alarm/event has been noticed.
Uninitialized
Setting:
•
Uninitialized
•
Acknowledged
•
Unacknowledged
UPDATE_STATE
Update State
R
A discrete enumeration which gives an indication of whether the
alert has been reported.
Uninitialized
Setting:
•
Uninitialized
•
Reported
•
Not Reported
TIME_STAMP
Time Stamp
R
The time when evaluation of the block was started and a change
in alarm/event state was detected that is unreported. The time
stamp value will be maintained constant until alert confirmation
has been received - even if another change of state occurs.
Uninitialized
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
STATIC_REVISION
Static Revision
R
The static revision of the block whose static parameter was
changed and is being reported. It is possible for the present value
of static revision to be greater than this because static can be
changed at any time.
0
Setting:
0…65535
RELATIVE_INDEX
Relative Index
R
The OD index of the static parameter whose change caused this
alert, minus the FB starting index. If the update event was caused
by a write to multiple parameters at the same time, then this
attribute will be zero.
0
Setting:
0…65535
CALIBRATION_CO
CALIBRATION_CO
CALIBRATION_CO
CALIBRATION_CO
NDITION
NDITION
NDITION
NDITION
Calibration
condition
Calibration condition
Transducer Block
Parameter
DD Name
Access
Description
settings
Initial