beautypg.com

Operation, 6 transducer block (tb) – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual

Page 30

background image

4

OPERATION

30

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

4.6 Transducer Block (TB)

The following tables list the Transducer Block parameters in alphabetical order.

It describes characteristics of the sensor output functions required to read the measurement
value from the Function Blocks.

The following tables contain short parameter description, factory settings (Initial Value (IV)) and
possible settings.

Foundation Fieldbus parameters for Transducer Block

Transducer Block

Parameter
DD Name

Access

Description
settings

Initial

ALERT_KEY

ALERT_KEY

ALERT_KEY

ALERT_KEY

Alert Key

RW

The identification number of the plant unit. This information may

be used in the host for sorting alarms, etc.

0

Setting:

1...255

BLOCK_ERR

BLOCK_ERR

BLOCK_ERR

BLOCK_ERR

Block Error

R

This parameter reflects the error status associated with the

hardware or software components associated with a block. It is a

bit string, so that multiple errors may be shown.

Other

Setting:

Other

BlockConfiguration

LinkConfiguration

SimulationActive

LocalOverride

DeviceFaultState

DeviceMaintenance

InputFailure

OutputFailure

MemoryFailure

LostStaticData

LostNVData

RbackCheck

MaintenanceNeeded

PowerUp

OutOfService

MODE_BLK

MODE_BLK

MODE_BLK

MODE_BLK

Block Mode

The actual, target, permitted and normal modes of the block.

TARGET

Target

RW

This is the mode requested by the operator. Only one mode from

those allowed by the permitted mode parameter may be

requested.

Auto

Setting:

Auto

OOS

ACTUAL

Actual

R

This is the current mode of the block, which may differ from the

target based on operating conditions. Its value is calculated as

part of block execution.

No Actual Mode

Setting:

Auto

OOS

PERMITTED

Permitted

RW

Defines the modes which are allowed for an instance of the block.

The permitted mode is configured based on application

requirement.

Auto and OOS

Setting:

Auto

OOS

AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 30 Friday, February 21, 2014 11:25 AM