Operation, Operation 4.1 getting started – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual

Page 11

background image

OPERATION

4

11

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

Operation

4.1 Getting started

The minimum configuration which has to be carried out in order to switch the Analog Input Block
from OOS (Out Of Service) to AUTO mode and to get a live measurement signal is as follows:

Analog Input Block (AI)

Please refer to chapter Analog Input Block (AI) for more detailed description of these
parameters.

If there are still problems to get started please execute a diagnosis as follows:
When looking to the parameter DIAGNOSIS_BLK at the Resource Block (RB) you can identify why
a block cannot be switched to AUTO mode or what has caused a Block Error. After solving the
issue the next diagnosis will be indicated in case of more than one cause.

Parameter

Recommended setting

Remarks

CHANNEL

1 = Volume Flow (e.g. l/h)

2 = Standard/Normal volume flow (e.g.

SCFH or Nl/h)

3 = Mass flow (e.g. kg/h)

Refer to EU (Engineering Units) on the

mechanical scale to determine the type

of flow

XD_SCALE

0 – Full Scale

Follow mechanical scale respectively

values from TB (Transducer Block) for

Range and EU

OUT_SCALE

0 – Full Scale

Follow mechanical scale respectively

values from TB (Transducer Block) for

Range and EU

L_TYPE

Direct

Linear function: Input = Output, same

dimensions

AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 11 Friday, February 21, 2014 11:25 AM