beautypg.com

Operation, 7 analog input block (ai) – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual

Page 40

background image

4

OPERATION

40

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

4.7 Analog Input Block (AI)

The following tables list the Analog Input Block parameters in alphabetical order.

It describes characteristics of the measurement values obtained from the Transducer Block in a
user defined way and to deliver it to the control system. There are also some parameters in the
Analog Input Block, that can be configured to get a measurement value quality as desired by the
user.

The following tables contain short parameter description, factory settings (Initial Value (IV)) and
possible settings.

Analog Input Block

Parameter
DD Name

Access

Description
settings

Initial

Alert Key

Alert Key

Alert Key

Alert Key

RW

The identification number of the plant unit. This information may

be used in the host for sorting alarms, etc.

0

Setting:

1...255

BLOCK_ERR

BLOCK_ERR

BLOCK_ERR

BLOCK_ERR

Block Error

R

This parameter reflects the error status associated with the

hardware or software components associated with a block. It is a

bit string, so that multiple errors may be shown.

OOS (Out of

Service)

Setting:

Other: Non-specific error active

BlockConfiguration: Error detected in block configuration

LinkConfiguration: Error detected in link configuration

SimulationActive: Simulation enabled in this block

LocalOverride: Output tracking of faultstate active

DeviceFaultState: Device faultstate set

DeviceMaintenance: Device needs maintenance soon

InputFailure: Process variable has bad status

OutputFailure: Failure detected in output hardware

MemoryFailure: Memory error detected

LostStaticData: Static parameters cannot be recovered

LostNVData: Non-Volatile parameters cannot be recovered

Readback Check: Failure detected in READBACK

MaintenanceNeeded: Device NEEDS maintenance NOW

PowerUp: Recovery from power failure

OutOfService: Block actual mode is out of service

MODE_BLK

MODE_BLK

MODE_BLK

MODE_BLK

Block Mode

The actual, target, permitted and normal modes of the block.

TARGET

Target

RW

This is the mode requested by the operator. Only one mode from

those allowed by the permitted mode parameter may be

requested.

OOS

Setting:

Auto

OOS

ACTUAL

Actual

R

This is the current mode of the block, which may differ from the

target based on operating conditions. Its value is calculated as

part of block execution.

OOS

Setting:

Auto

OOS

AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 40 Friday, February 21, 2014 11:25 AM