Operation – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual
Page 48
4
OPERATION
48
H250 M40
www.krohne.com
02/2014 - 4001208201 - AD H250 M40 FF R02 en
SUBCODE
Subcode
R
An enumeration specifying the cause of the alert to be reported.
Other
Setting:
•
Other
•
BlockConfiguration
•
LinkConfiguration
•
SimulationActive
•
LocalOverride
•
DeviceFaultState
•
DeviceMaintenance
•
InputFailure
•
OutputFailure
•
MemoryFailure
•
LostStaticData
•
LostNVData
•
RbackCheck
•
MaintenanceNeeded
•
PowerUp
•
OutOfService
VALUE
Float Value
R
A numerical quantity entered by a user or calculated by the
algorithm.
0.0
LO_LIM
LO_LIM
LO_LIM
LO_LIM
Low Limit
RW
The setting for the low alarm in engineering units.
(-NaN)
Setting:
-3.39E38…+3.39E38 / -INF (-infinite) / + INF (+infinite)
LO_LO_LIM
LO_LO_LIM
LO_LO_LIM
LO_LO_LIM
Low Low Limit
RW
The setting for the low alarm in engineering units.
(-NaN)
Setting:
-3.39E38…+3.39E38 / -INF (-infinite) / + INF (+infinite)
LO_LO_PRI
LO_LO_PRI
LO_LO_PRI
LO_LO_PRI
Low Low Priority
RW
Priority of the low low alarm.
0
Setting:
0...15
LO_PRI
LO_PRI
LO_PRI
LO_PRI
Low Priority
RW
Priority of the low alarm.
0
Setting:
0...15
LOW_CUT
LOW_CUT
LOW_CUT
LOW_CUT
Low Cutoff
RW
Limit used in square root processing. A value of zero percent of
scale is used in block processing if the transducer value falls
below this limit, in % of scale. This feature may be used to
eliminate noise near zero from a flow sensor.
0.0
Setting:
≥ 0.0
OUT
OUT
OUT
OUT
Output
The primary analog value calculated as a result of executing the
function block.
STATUS
Status
R
Digital transducers, unlike their analog versions, can detect faults
that make the measurement bad or prevent the actuator from
responding. This additional, valuable information will be passed
along with each transmission of a data value in the form of a
status attribute.
VALUE
Value
RW
A numerical quantity entered by a user or calculated by the
algorithm.
0.0
OUT_SCALE
OUT_SCALE
OUT_SCALE
OUT_SCALE
Output Scale
The high and low scale values, engineering units code, and
number of digits to the right of the decimal point to be used in
displaying the OUT parameter and parameters which have the
same scaling as OUT.
EU_100
EU at 100%
RW
The engineering unit value which represents the upper end of
range of the associated block parameter.
100.0
EU_0
EU at 0%
RW
The engineering unit value which represents the lower end of
range of the associated block parameter.
0.0
UNITS_INDEX
Units Index
RW
Device Description units code index for the engineering unit
descriptor for the associated block value.
Every Unit possible.
Uninitialized
Analog Input Block
Parameter
DD Name
Access
Description
settings
Initial
AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 48 Friday, February 21, 2014 11:25 AM