OPERATION

4

55

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

INTEG_OPTS

INTEG_OPTS

INTEG_OPTS

INTEG_OPTS

Integration Options

Integration Options

Integration Options

Integration Options

RW

INTEG_OPTS is to be used to specify several integration

options as type of input used in each input, flow direction to be

considered in the totalization, status to be considered in the

totalization and if the totalization residue shall be used in the

next batch after a reset.

Uninitialized

The following INTEG_OPTS are possible (see also

INTEG_TYPE):

Input 1 accumulate: IN_1 is used as pulse (otherwise as rate)

Input 2 accumulate: IN_2 is used as pulse (otherwise as rate)

Flow forward: only positive net flow will be taken into
account for totalization

Flow reverse: only negative net flow will be taken into
account for totalization

Use Uncertain: IN_1 and IN_2 input will be taken into
account even if their states are "Uncertain" (otherwise the
value with the last "Good" status will be taken)

Use BAD Input: IN_1 or IN_2 with "Bad" status will be
interpreted as "Good" (Note: only the status is interpreted as
"Good", the value isn't used for totalization, but the good one,
i.e. RTOTAL isn't affected with this setting.

Carry: integration after a reset starts with the init value, but
with the residual after the trip value.

Add zero if Bad: if one of the input (IN_1 or IN_2) statuses are
"Bad", not the last "Good" value is used for totalization, but
zero (0).

Confirm reset: after a manual reset of totalization, the next
manual reset must be preceded by a reset confirmation by
the control system.

Generate reset event: in case of reset (automatic or manual),
an event notification will be sent to the control system.
(This function is an option and not supported.)

N_RESET

N_RESET

N_RESET

N_RESET

Number of Reset

Number of Reset

Number of Reset

Number of Reset

R

Counts the number of resets. It can not be written nor reset.

OP_CMD_INT

OP_CMD_INT

OP_CMD_INT

OP_CMD_INT

Operator

Operator

Operator

Operator

Command

Command

Command

Command

Integration

Integration

Integration

Integration

RW

Operator command. "Reset" resets the totalizer.

Off

Setting:

0: Off / 1: Reset

OUT

OUT

OUT

OUT

Output

Output

Output

Output

RW

The primary analog value calculated as a result of executing

the function. The display scaling for the corresponding output.

It has no effect on the block.

Status

R

Actual status of Output.

Value

R

Actual value

OUT_PTRIP

OUT_PTRIP

OUT_PTRIP

OUT_PTRIP

Output Pre Trip

Output Pre Trip

Output Pre Trip

Output Pre Trip

R/W

The second discrete output.

Status

RW

Setting:

Good Non Cascade / Good Cascade / Uncertain / Bad Not

Connected / Bad

Bad Not Connected

Value

RW

Setting:

0: Off / 1: On

Off

OUT_RANGE

OUT_RANGE

OUT_RANGE

OUT_RANGE

Output Range

Output Range

Output Range

Output Range

RW

This is the display scaling for the output. It has no effect on the

block.

EU_100

Engineering Unit

100

RW

The engineering unit value which represents the upper end of

range of the associated block parameter.

100.0

Integrator Block

Parameter
DD Name

Access

Description
settings

Initial