beautypg.com

Operation – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual

Page 41

background image

OPERATION

4

41

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

PERMITTED

Permitted

RW

Defines the modes which are allowed for an instance of the block.

The permitted mode is configured based on application

requirement.

OOS

Auto

Setting:

Auto

OOS

NORMAL

Normal

RW

This is the mode which the block should be set to during normal

operating conditions.

Auto

Setting:

Auto

OOS

ST_REV

ST_REV

ST_REV

ST_REV

Static Revision

R

The revision level of the static data associated with the function

block. The revision value will be incremented each time a static

parameter value in the block is changed.

0

Setting:

0...65635

STRATEGY

STRATEGY

STRATEGY

STRATEGY

Strategy

RW

The strategy field can be used to identify grouping of blocks. This

data is not checked or processed by the block.

0

Setting:

0...65635

TAG_DESC

TAG_DESC

TAG_DESC

TAG_DESC

Tag Description

RW

This is the user description of the block.

blanks

Setting:

≤32 digits

ACK_OPTION

ACK_OPTION

ACK_OPTION

ACK_OPTION

Acknowledge

Option

RW

Selection of whether alarms associated with the function block

will be automatically acknowledged.

Uninitialized

Setting:

HiHi Alm Auto Ack

Hi Alm Auto Ack

LoLo Alm Auto Ack

Lo Alm Auto Ack

Blk Alm Auto Ack

Fail Alm Auto Ack

Off Spec

Alm Auto Ack

Maint Alm Auto Ack

Check Alm Auto Ack

ALARM_HYS

ALARM_HYS

ALARM_HYS

ALARM_HYS

Alarm Hystresis

RW

Amount the PV must return within the alarm limits before the

alarm condition clears. Alarm Hysteresis is expressed as a

percent of the span of the PV.

0.5

Setting:

0...50%

ALARM_SUM

ALARM_SUM

ALARM_SUM

ALARM_SUM

Alarm Summary

The current alert status, unacknowledged states, unreported

states and disabled states of the alarms associated with the

function block.

CURRENT

Current

R

The active status of each alarm.

Uninitialized

Setting:

HiHi Alarm

Hi Alarm

LoLo Alarm

Lo Alarm

Block Alarm

Analog Input Block

Parameter
DD Name

Access

Description
settings

Initial

AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 41 Friday, February 21, 2014 11:25 AM