Operation – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual
Page 18
4
OPERATION
18
H250 M40
www.krohne.com
02/2014 - 4001208201 - AD H250 M40 FF R02 en
FEATURES_SEL
FEATURES_SEL
FEATURES_SEL
FEATURES_SEL
Features Selection
RW
Used to select resource block options.
•
Reports
•
Faultstate
•
Soft W Lock
Setting:
•
Reports
•
Faultstate
•
Soft W Lock
•
MVC Report Distribution supported
•
MVC Publishing/Subscribing supported
•
Multi-bit Alarm (Bit-Alarm) Support
FREE_SPACE
FREE_SPACE
FREE_SPACE
FREE_SPACE
Free Space
R
Percent of the memory available for further configuration.
Zero in a preconfigured device.
0.0
Setting:
0.0…100.0
FREE_TIME
FREE_TIME
FREE_TIME
FREE_TIME
Free Time
R
Percent of the block processing time that is free to process
additional blocks.
0.0
Setting:
0.0…100.0
GRANT_DENY
GRANT_DENY
GRANT_DENY
GRANT_DENY
Grant Deny
RW
Options for controlling access of host computers and local
control panels to operating, tuning and alarm parameters of
the block.
GRANT
Grant
RW
Depending on the philosophy of the plant, the operator or a
higher level device (HLD) or a local operator's panel (LOP) in
the case of "Local", may turn on an item of the "Grant"
attribute - "Program, Tuning, Alarm or Local".
Uninitialized
Setting:
•
Program
•
Tune
•
Alarm
•
Local
DENY
Deny
RW
The Denied attribute is provided for use by a monitoring
application in an interface device and may not be changed by
an operator.
Uninitialized
Setting:
•
Program denied
•
Tune denied
•
Alarm denied
•
Local denied
HARD_TYPES
HARD_TYPES
HARD_TYPES
HARD_TYPES
Hardware Types
R
The types of hardware available as channel numbers.
Scalar input
ITK_VER
ITK_VER
ITK_VER
ITK_VER
ITK Version
R
Major revision number of the interoperability test case used to
register this device.
5
LIM_NOTIFY
LIM_NOTIFY
LIM_NOTIFY
LIM_NOTIFY
Limit Notify
RW
Maximum number of unconfirmed notify messages allowed.
20
Setting:
0...255
MANUFAC_ID
MANUFAC_ID
MANUFAC_ID
MANUFAC_ID
Manufacturer ID
R
Manufacturer identification number - used by an interface
device to locate the DD file for the resource.
KROHNE
MAX_NOTIFY
MAX_NOTIFY
MAX_NOTIFY
MAX_NOTIFY
Maximum Notify
R
Maximum number of unconfirmed notify messages possible.
20
Setting:
0...255
MEMORY_SIZE
MEMORY_SIZE
MEMORY_SIZE
MEMORY_SIZE
Memory Size
R
Available configuration memory in the empty resource. To be
checked before attempting a download.
0
MIN_CYCLE_T
MIN_CYCLE_T
MIN_CYCLE_T
MIN_CYCLE_T
Minimium Cycle Time
R
Time duration of the shortest cycle interval of which the
resource is capable.(in [1/32 ms])
6400
Foundation Fieldbus parameters for Resource Block
Parameter
DD Name
Access
Description
Settings
Initial