4
OPERATION
42
H250 M40
www.krohne.com
02/2014 - 4001208201 - AD H250 M40 FF R02 en
UNACKNOWLEDG
ED
Unacknowledged
R
The unacknowledged state of each alarm.
Uninitialized
Setting:
•
HiHi Alarm
•
Hi Alarm
•
LoLo Alarm
•
Lo Alarm
•
Block Alarm
UNREPRTED
Unreported
R
The unreported status of each alarm.
Uninitialized
Setting:
•
HiHi Alarm
•
Hi Alarm
•
LoLo Alarm
•
Lo Alarm
•
Block Alarm
DISABLED
Disabled
R
The disabled state of each alarm.
Uninitialized
Setting:
•
HiHi Alarm
•
Hi Alarm
•
LoLo Alarm
•
Lo Alarm
•
Block Alarm
BLOCK_ALM
BLOCK_ALM
BLOCK_ALM
BLOCK_ALM
Block Alarm
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause of
the alert is entered in the subcode field. The first alert to become
active will set the "Active" status in the "Status" attribute. As soon
as the "Unreported" status is cleared by the alert reporting task,
another block alert may be reported without clearing the "Active"
status, if the subcode has changed.
UNACKNOWLEDG
ED
Unacknowledged
RW
A discrete enumeration which is set to "Unacknowledged" when
an alarm occurs, and set to "Acknowledged" by a write from a
human interface device or other entity which can acknowledge
that the alarm/event has been noticed.
Uninitialized
Setting:
•
Uninitialized
•
Acknowledged
•
Unacknowledged
ALAMSTATE
Alarm State
R
A discrete enumeration which gives an indication of whether the
alert is active and whether it has been reported.
Uninitialized
Setting:
•
Uninitialized
•
Clear-Reported
•
Clear-Not Reported
•
Active-Reported
•
Active-Not Reported
TIME_STAMP
Time Stamp
R
The time when evaluation of the block was started and a change
in alarm/event state was detected that is unreported. The time
stamp value will be maintained constant until alert confirmation
has been received - even if another change of state occurs.
Uninitialized
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
Analog Input Block
Parameter
DD Name
Access
Description
settings
Initial