beautypg.com

Operation – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual

Page 15

background image

OPERATION

4

15

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

PERMITTED

Permitted

RW

Defines the modes which are allowed for an instance of the

block. The permitted mode is configured based on application

requirement.

Auto

OOS

Setting:

Auto

OOS

NORMAL

Normal

RW

This is the mode the block should be set to during normal

operating conditions.

Auto

Setting:

Auto

OOS

ST_REV

ST_REV

ST_REV

ST_REV

Static Revision

R

The revision level of the static data associated with the

function block. The revision value will be incremented each

time a static parameter value in the block is changed.

0

Setting:

0...65635

STRATEGY

STRATEGY

STRATEGY

STRATEGY

Strategy

R/W

The strategy field can be used to identify grouping of blocks.

This data is not checked or processed by the block.

0

Setting:

0...65635

TAG_DESC

TAG_DESC

TAG_DESC

TAG_DESC

Tag Description

RW

The user description of the intended application of the block.

blanks

Setting:

≤32 digits

ACK_OPTION

ACK_OPTION

ACK_OPTION

ACK_OPTION

Acknowledge Option

R/W

Selection of whether alarms associated with the function

block will be automatically acknowledged.

Uninitialized

Setting:

Disc Alm Auto Ack

Blk Alm Auto Ack

Fail Alm Auto Ack

Off Spec Alm Auto Ack

Maint Alm Auto Ack

Check Alm Auto Ack

ALARM_SUM

ALARM_SUM

ALARM_SUM

ALARM_SUM

Alarm Summary

The current alert status, unacknowledged states, unreported

states and disabled states of the alarms associated with the

function block.

CURRENT

Current

R

The active status of each alarm.

Uninitialized

Setting:

Discrete Alarm

Block Alarm

Fail Alarm

Off Spec Alarm

Maintenance Alarm

Check Alarm

UNACKNOWLEDGED

Unacknowledged

R

The unacknowledged state of each alarm.

Uninitialized

Setting:

Disc Alm Unack

Block Alm Unack

Fail Alm Unack

Off Spec Alm Unack

Maint Alm Unack

Check Alm Unack

Uninitialized

UNREPRTED

Unreported

R

The unreported state of each alarm.

Uninitialized

Setting:

Disc Alm Unrep

Block Alm Unrep

Fail Alm Unrep

Off Spec Alm Unrep

Maint Alm Unrep

Check Alm Unrep

Foundation Fieldbus parameters for Resource Block

Parameter
DD Name

Access

Description
Settings

Initial

AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 15 Friday, February 21, 2014 11:25 AM