Operation – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual

Page 36

background image

4

OPERATION

36

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

UNITS_INDEX

Units Index

RW

Device Description units code index for the engineering unit

descriptor for the associated block value.

l/h

Setting:

m

3

/s, min, h, d

l/s, min, h, d

Ml/d

ft

3

/s, min, h, d

gal/s, min, h, d

Mgal/d

ImpGal/s, min, h, d

bbl/s, min, h, d

cm

3

/s, min, h, d

kl/min, h, d

ml/min

DECIMAL

Decimal

R

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the specified

parameter.

0

PRIMARY_VALUE_

PRIMARY_VALUE_

PRIMARY_VALUE_

PRIMARY_VALUE_

TYPE_2

TYPE_2

TYPE_2

TYPE_2

Primary Value

Type

R

The type of measurement represented by the primary value. For

Example:

Mass Flow, Absolute Pressure, Differential Temperature.

volumentric flow

PRIMARY_VALUE_

PRIMARY_VALUE_

PRIMARY_VALUE_

PRIMARY_VALUE_

2222

gas volume flow

The measured gas volume flow value and status of available to

the Function Block.

STATUS

Status

R

Digital transducers, unlike their analog versions, can detect faults

that make the measurement bad or prevent the actuator from

responding. This additional, valuable information will be passed

along with each transmission of a data value in the form of a

status attribute.

VALUE

Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

PRIMARY_VALUE_

PRIMARY_VALUE_

PRIMARY_VALUE_

PRIMARY_VALUE_

RANGE_2

RANGE_2

RANGE_2

RANGE_2

gas volume flow

range

The High and Low range limit values, the engineering units code

and the number of digits to the right of the decimal point to be

used to display the Primary Value.

EU_100

max value

R

The engineering unit value which represents the upper end of

range of the associated block parameter.

100

EU_0

min value

R

The engineering unit value which represents the lower end of

range of the associated block parameter.

0.0

UNITS_INDEX

Units Index

RW

Device Description units code index for the engineering unit

descriptor for the associated block value.

Nl/h

Setting:

SCFM

SCFH

Nm

3

/s, min, h, d

Sm

3

/s, min, h, d

Nl/s, min, h, d

Sl/s, min, h, d

MSCFD

MMSCFD

DECIMAL

Decimal

R

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the specified

parameter.

0

PRIMARY_VALUE_

PRIMARY_VALUE_

PRIMARY_VALUE_

PRIMARY_VALUE_

TYPE_3

TYPE_3

TYPE_3

TYPE_3

Primary Value

Type

The measured mass flow value and status of available to the

Function Block.

STATUS

Status

R

Digital transducers, unlike their analog versions, can detect faults

that make the measurement bad or prevent the actuator from

responding. This additional, valuable information will be passed

along with each transmission of a data value in the form of a

status attribute.

Transducer Block

Parameter
DD Name

Access

Description
settings

Initial

AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 36 Friday, February 21, 2014 11:25 AM