DECIMAL

Decimal

RW

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the specified

parameter.

0

PV

PV

PV

PV

Process Value

Either the primary analog value for use in executing the function,

or a process value associated with it. May also be calculated from

the RBACK value of an AO block.

STATUS

Status

R

Digital transducers, unlike their analog versions, can detect faults

that make the measurement bad or prevent the actuator from

responding. This additional, valuable information will be passed

along with each transmission of a data value in the form of a

status attribute.

0

VALUE

Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

PV_FTIME

PV_FTIME

PV_FTIME

PV_FTIME

Process Value

Filter Time

RW

Time constant of a single exponential filter for the PV, in seconds. 0.0

Setting:

0.0...60.0

SIMULATE

SIMULATE

SIMULATE

SIMULATE

Simulate

Allows the transducer analog input or output to the block to be

manually supplied when simulate is enabled. When simulate is

disabled, the simulate value and status track the actual value and

status.

SIMULATE_STATU

S

Simulate Status

RW

Used for the transducer status when simulation is enabled.

0

SIMULATE_VALUE

Simulate Value

RW

Used for the transducer value when simulation is enabled.

0.0

Setting:

-3.39E38…+3.39E38 / -INF (-infinite) / + INF (+infinite)

TRANSDUCER_VA

LUE

Transducer Value

R

Current value supplied by the transducer.

0.0

ENABLE_DISABLE

Simulate

En/Disable

RW

Enable/disable simulation.

Disabled

Setting:

Uninitialized

Disabled

Active

STATUS_OPTS

STATUS_OPTS

STATUS_OPTS

STATUS_OPTS

Status Options

RW

Options which the user may select in the block processing of

status.

Uninitialized

Setting:

Propagate Fault Fwd

Uncertain if Limited

Bad if Limited

Uncertain if Man.

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

Update Event

This alert is generated by any change to the static data.

UNACKNOWLEDG

ED

Unacknowledged

RW

A discrete enumeration which is set to Unacknowledged when an

update occurs, and set to Acknowledged by a write from a human

interface device or other entity which can acknowledge that the

alarm has been noticed.

Uninitialized

Setting:

Uninitialized

Acknowledged

Unacknowledged

Analog Input Block

Parameter
DD Name

Access

Description
settings

Initial

AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 49 Friday, February 21, 2014 11:25 AM