Operation – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual
Page 54
4
OPERATION
54
H250 M40
www.krohne.com
02/2014 - 4001208201 - AD H250 M40 FF R02 en
Value
R
The value of the associated parameter at the time the alert
was detected.
0
Setting:
0...255
CLOCK_PER
CLOCK_PER
CLOCK_PER
CLOCK_PER
Clock Period
Clock Period
Clock Period
Clock Period
RW
Establishes the period for periodic reset, in seconds.
0
Setting:
Positive or 0
GOOD_LIM
GOOD_LIM
GOOD_LIM
GOOD_LIM
Good Limit
Good Limit
Good Limit
Good Limit
RW
Sets the limit for PCT_INCL. Below this limit OUT receives the
status good.
0
Setting:
0...100%
GRANT_DENY
GRANT_DENY
GRANT_DENY
GRANT_DENY
Grant Deny
Grant Deny
Grant Deny
Grant Deny
RW
Options for controlling access of host computers and local
control panels to operating, tuning and alarm parameters of
the block.
Grant
R/W
Depending on the philosophy of the plant, the operator or a
higher level device (HLD), or a local operator's panel (LOP) in
the case of Local, may turn on an item of the Grant attribute -
Program, Tune, Alarm or Local.
Uninitialized
Setting:
Program / Tune / Alarm / Local
Deny
RW
The Denied attribute is provided for use by a monitoring
application in an interface device and may not be changed by
an operator.
Uninitialized
Setting:
Program denied / Tune denied / Alarm denied / Local denied
IN_1
IN_1
IN_1
IN_1
Input 1
Input 1
Input 1
Input 1
RW
Input 1 of the Integrator Block.
Status
Status of IN_1
Value
Actual value
IN_2
IN_2
IN_2
IN_2
Input 2
Input 2
Input 2
Input 2
RW
Input 2 of the Integrator Block.
Status
Status of IN_2
Value
Actual value
OUT_PTRIP
OUT_PTRIP
OUT_PTRIP
OUT_PTRIP
Output Pre Trip
Output Pre Trip
Output Pre Trip
Output Pre Trip
RW
The second discrete output.
Status
RW
Setting:
Good Non Cascade / Good Cascade / Uncertain / Bad Not
Connected / Bad
Bad Not Connected
Value
RW
Setting:
0: Off / 1: On
0
Integrator Block
Parameter
DD Name
Access
Description
settings
Initial