Operation – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual
Page 43
OPERATION
4
43
H250 M40
www.krohne.com
02/2014 - 4001208201 - AD H250 M40 FF R02 en
SUBCODE
Subcode
R
An enumeration specifying the cause of the alert to be reported.
Other
Setting:
•
Other
•
BlockConfiguration
•
LinkConfiguration
•
SimulationActive
•
LocalOverride
•
DeviceFaultState
•
DeviceMaintenance
•
InputFailure
•
OutputFailure
•
MemoryFailure
•
LostStaticData
•
LostNVData
•
RbackCheck
•
MaintenanceNeeded
•
PowerUp
•
OutOfService
VALUE
Value
R
The value of the associated parameter at the time the alert was
detected.
0
Setting:
0...255
CHANNEL
CHANNEL
CHANNEL
CHANNEL
Channel
RW
The number of the logical hardware channel that is connected to
this I/O block. This information defines the transducer to be used
going to or from the physical world.
Uninitialized
Setting:
0 Uninitialized
1. volume flow
2. gas volume flow
3. mass flow
4. level
5. electronic temperature
FIELD_VAL
FIELD_VAL
FIELD_VAL
FIELD_VAL
Field Value
Field Value
Field Value
Field Value
Raw value of the field device in percent of the PV range, with a
status reflecting the transducer condition, before signal
characterization (L_TYPE) or filtering (PV_FTIME).
STATUS
Status
R
Digital transducers, unlike their analog versions, can detect faults
that make the measurement bad or prevent the actuator from
responding. This additional, valuable information will be passed
along with each transmission of a data value in the form of a
status attribute.
Bad:NonSpecific:N
otLimited
VALUE
Value
R
A numerical quantity entered by a user or calculated by the
algorithm.
0.0
GRANT_DENY
GRANT_DENY
GRANT_DENY
GRANT_DENY
Grant Deny
Options for controlling access of host computers and local control
panels to operating, tuning and alarm parameters of the block.
GRANT
Grant
RW
Depending on the philosophy of the plant, the operator or a higher
level device (HLD) or a local operator's panel (LOP) in the case of
"Local", may turn on an item of the "Grant" attribute - "Program,
Tune, Alarm or Local".
Uninitialized
Setting:
•
Program
•
Tune
•
Alarm
•
Local
•
Operate
DENY
Deny
RW
The Denied attribute is provied for use by a monitoring application
in an interface device and may not be changed by an operator.
Uninitialized
Setting:
•
Program Denied
•
Tune Denied
•
Alarm Denied
•
Local Denied
•
Operate Denied
Analog Input Block
Parameter
DD Name
Access
Description
settings
Initial
AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 43 Friday, February 21, 2014 11:25 AM