beautypg.com

KROHNE UFM 600T EN User Manual

Page 86

background image

Ambient temp.

-25 to +50 °C (-13 to 122°F)

Protection
category

IP 65, acc. to IEC 529
(equivalent to NEMA 4x)

Full scale value

(Din= inner pipe diameter)

lower limit

(V

100% min

. = 0.5 m/s)

Q

100%min

[m

3

/h]

= ( Din [mm]/100 )

2

* 14.2

Q

100%min

[m

3

/h] = ( Din [inch] )

2

* 0.9

Q

100%min

[USGPM] = ( Din [inch])

2

* 3.9

upper limit

(V

100%max

= 17.1 m/s)

Q

100%max

[m3/h] = (Din [mm] )

2

* 0.05

Q

100%max

[m3/h] = (Din [inch] )

2

* 31.25

Q

100%max

[USGPM] = (Din [inch] )

2

* 138

Reynolds
number

Re > 10.000

Repeatability

0.2

R =

[%]

V

m

*D

i

R

=

repeatability in %

V

m

=

flow velocity [m/s]

D

i

=

inner pipe diameter [m]

83