D.6

Parameter errors

If discrepancies in the parameters entered are found the
microprocessor will display the message "PARAMERROR"
thus preventing you from storing parameters that are incor-
rect.

The PARAMERROR menu can appear at the end of both the
Start Up menu and the Installation Menu.

A third main menu is available now:
Fct. 4.0.0 PARAM.ERROR

In this menu only one submenu is available at a time; only the
submenu that applies to the discrepancy to be corrected will
be displayed.

List of possible submenus and functions within PARAMER-
ROR:

4.0.0

PARAMERROR

Discrepancy:

4.1.0

V RANGE

The combination of the diame-
ter, wall and lining thickness and the full
scale flow rate is not feasible.

4.1.1

DIAMETER

4.1.2

PIPEWALL

4.1.3

LINING TH.

4.1.4

FULL SCALE

4.2.0

I RANGE

[I 100 PCT] does not exceed
[I 0 PCT] by at least 4 mA

4.2.1

I 0 PCT

4.2.2

I 100 PCT

4.3.0

I MAX mA

[I MAX] is not equal to or greater
than [I 100 PCT]

4.3.1

I 100 PCT

4.3.2

I MAX

4.4.0

CUTOFF

CUTOFF ON exceeds CUTOFF OFF

74

ALTOSONIC

Programming mode

UFM 600 T