Altosonic – KROHNE UFM 600T EN User Manual
Page 43
C.5
Quit / Reset Menu
The measuring mode can be exited with the code as
described below to enter the Quit/Reset Menu.
In this menu two functions can be used:
ERRORLIST:
Show the list of errors indicated by the * sign at the left-hand
side of the display.
When the error messages are not programmed to appear on
a regular display (function 3.2.4 and 3.6.4) the only way to
recognize an error (apart from the low signal marker) is by the
* sign at the left-hand side of the display.
Enter the error list with the key; the number of errors and
the first error message will be visible. Use the key to dis-
play the other error(s); eventually the ERR.ACQUIT function
will appear.
ERR.ACQUIT
function:
After curing the cause of the error(s) enter the ERR.ACQUIT
function by using the key and select YES with key to
reset the error message and error marker *.
Even if the cause of an error is cured the error message and
the error marker will not disappear until they are cleared by
the ERR.ACQUIT function.
Use the key to leave the function.
Use the key to return to the measuring mode.
*
Note that these error messages differ from those included
in the data block that is stored and sent to the RS 232
output at regular intervals (function 3.2.4 and 3.6.4) :
at the end of the next complete data collection interval
following the elimination of the errors these messages will
have disappeared automatically.
42
ALTOSONIC
Operation
UFM 600 T