beautypg.com

KROHNE UFM 600T EN User Manual

Page 60

background image

3.2.0 DISPLAY

:

set output functions
L.C.display

NOTE:

All functions that are programmed to be on display can also
be saved as programmed in function 3.6.3

SEL.COMM.

3.2.1 DISP. FLOW

:

Display Flow rate

Determine whether the flow rate should be displayed and if
so, in what sort of units; select a display option using the

key and press to store:

NO DISPLAY :
m3/Sec

:

m3/min

:

m3/hr

:

Liter/Sec

:

Liter/min

:

Liter/hr

:

US G/Sec

:

U.S. Gallon per second

US G/min

:

US G/hr

:

——-/—-

:

reserved for user defined unit

PERCENT

:

percentage of full scale as entered
in Start Up menu

3.2.2 DISP. TOTAL

:

Display Totalisator
outputs

Select which totalizer outputs should be displayed by using
the key and press to store:

NO DISPLAY :

(function 3.2.3 will not appear)

+ TOTAL

:

Totalizer for positive flow

- TOTAL

:

Totalizer for negative flow

+/- TOTAL

:

Totalizers for both positive and
negative flow

SUM TOTAL

:

[+ TOTAL]- [- TOTAL]

ALL TOTAL

:

All three totalizer options are active

57