Technical data – KROHNE OPTISWIRL 4070 EN User Manual
Page 71
TECHNICAL DATA
8
71
OPTISWIRL 4070
www.krohne.com
02/2013 - 4000150606 MA OPTISWIRL4070C R07 en
Measuring accuracy
Reference condition
Water at 20ºC
Air at 20°C and 1.013 bar abs.
Accuracy
Based on volume flow
Liquids
±
0.75% of measured value (Re ≥ 20000)
±
2.0% of measured value (10000 < Re < 20000)
Gases and steams
±
1.0% of measured value (Re ≥ 20000)
±
2.0% of measured value (10000 < Re < 20000)
Pressure and temperature compensation: ±1.5% of measured value (Re ≥ 20000);
±
2.5% of measured value (10000 < Re < 20000)
Repeatability
±
0.1% of measured value
Long-term stability
±
0.01% of measured value
Operating conditions
Temperature
Product
-40…+240°C / -40…+465°F
Ambient
Non-Ex: -40…+85°C / -40…+185°F
Ex: -40…+60°C / -40…+140°F
Storage
-50…+85°C / -58…+185°F
Pressure
Product
Max. 100 bar / 1450 psi; Information on higher pressures on request.
Ambient
Atmosphere
Chemical properties
Density
Taken into consideration when sizing.
Viscosity
< 10 cP
Reynold's number
10000...2300000
Recommended flow velocities
Liquids
0.3…7 m/s / 0.98…23 ft/s (optional up to 10 m/s / 32.8 ft/s taking cavitation into
account)
Gases and steams
2.0…80 m/s / 6.6…262.5 ft/s
DN15: 3.0…45 m/s / 9.8…148 ft/s; DN25: 2.0…70 m/s / 6.6…230 ft/s
For detailed information, see chapter "Flow tables".
Other conditions
Protection category
IP 66/67