TECHNICAL DATA

8

71

OPTISWIRL 4070

www.krohne.com

02/2013 - 4000150606 MA OPTISWIRL4070C R07 en

Measuring accuracy

Reference condition

Water at 20ºC

Air at 20°C and 1.013 bar abs.

Accuracy

Based on volume flow

Liquids

±

0.75% of measured value (Re ≥ 20000)

±

2.0% of measured value (10000 < Re < 20000)

Gases and steams

±

1.0% of measured value (Re ≥ 20000)

±

2.0% of measured value (10000 < Re < 20000)

Pressure and temperature compensation: ±1.5% of measured value (Re ≥ 20000);
±

2.5% of measured value (10000 < Re < 20000)

Repeatability

±

0.1% of measured value

Long-term stability

±

0.01% of measured value

Operating conditions

Temperature

Product

-40…+240°C / -40…+465°F

Ambient

Non-Ex: -40…+85°C / -40…+185°F

Ex: -40…+60°C / -40…+140°F

Storage

-50…+85°C / -58…+185°F

Pressure

Product

Max. 100 bar / 1450 psi; Information on higher pressures on request.

Ambient

Atmosphere

Chemical properties

Density

Taken into consideration when sizing.

Viscosity

< 10 cP

Reynold's number

10000...2300000

Recommended flow velocities

Liquids

0.3…7 m/s / 0.98…23 ft/s (optional up to 10 m/s / 32.8 ft/s taking cavitation into

account)

Gases and steams

2.0…80 m/s / 6.6…262.5 ft/s

DN15: 3.0…45 m/s / 9.8…148 ft/s; DN25: 2.0…70 m/s / 6.6…230 ft/s

For detailed information, see chapter "Flow tables".

Other conditions

Protection category

IP 66/67