3.6 Installation

3.6.1 General installation notes

The following procedures have to be carried out before installing the device:

• Remove all transportation safety devices and protective coverings from the device.
• Ensure that the gaskets have the same diameter as the pipelines.
• Note the correct flow direction for the device. This is indicated by an arrow on the housing of

the measuring sensor.

• On metering points with varying thermal loads, the flowmeters have to be mounted with stress

bolts (DIN 2510).

• Stress bolts or bolts and nuts are not included in the scope of delivery.
• Ensure that the measuring flange is concentrically fitted.
• Note the exact installation length of the measuring device when preparing the metering point.

CAUTION!
Installation, assembly, start-up and maintenance may only be performed by appropriately
trained personnel. The regional occupational health and safety directives must always be
observed.

Figure 3-10: Preparing the metering point

1 Installation length of measuring device + thickness of gaskets.

CAUTION!
The internal diameter of the pipelines, the measuring sensor and the gaskets must match. The
gaskets may not protrude into the flow.

Figure 3-11: Internal diameter

1 Internal diameter connection pipe
2 Internal diameter flange and gasket
3 Internal diameter measuring sensor