OPERATION

46

OPTISWIRL 4070

www.krohne.com

02/2013 - 4000150606 MA OPTISWIRL4070C R07 en

Totalizer / pulse output

The base units for the totalizer and the pulse output are m

m

m

m

3

33

3

for volume,

m

m

m

m

3

33

3

norm. for standard volume and kg

kg

kg

kg for mass.

The unit and the conversion factor can be changed in menu item 3.2.8 "Tot.Conf.". User defined
units (User Def.) can be selected and entered. The conversion factor of the unit must always be
entered based on the base unit.

The maximum pulse output frequency is 0.5 Hz. To ensure that the pulse output does not exceed
0.5 Hz, the conversion factor of the totalizer must be selected and set accordingly. The pulse
output represents an exact copy of the whole number value of the internal totalizer.

Max. pulses per hour

Example

Menu items

6.2.6 Measures in the event of faulty indications

If the indications on the display or the responses to keypad commands are faulty, you have to do
a hardware reset. Switch the power supply OFF and ON again.

fmax. ≤ 0.5 Hz

1 pulse-break ≥ 2 seconds

Max. pulses / hour = 1800

1800

1800

1800 pulses

Flow Qmax.

Factor A1 Coef.

Pulses / litre

Pulses / h

Comment

5.6 m

3

/h

0.001

1 pulse / 1 litre

5600

not possible

0.01

1 pulse / 10 litres

560

560 < 1800 = ok.

1.1.3

Maes.Inst

Volume / Standard volume / Mass

1.1.4

Max. Flow

Unit (User Def.) / Text / A1 Coeff. / Max. Flow

Max. Flow

Max. Flow

Max. Flow / Flow Displ

3.2.5

Function P

Yes

Yes

Yes

Yes / No

3.2.7

Totalizer

Tot. on

Tot. on

Tot. on

Tot. on / Tot. off

3.2.8

Tot. Conf.

User def. / Unit Text / A1 Coeff.

User def. / Unit Text / A1 Coeff.

User def. / Unit Text / A1 Coeff.

User def. / Unit Text / A1 Coeff. / Preset Value / Reset / Display