6.5.4 Menu item Quick Setup

Level

Designation

Selection / entry field

Explanation

1.1.1

Language

Select menu language

German ↑...

German language

French ↑…

French language

English ↑...^

English language

1.1.2

Location

0000000000

Location↑…↑...↑...^

Enter the name of the location (max.

10 characters)

1.1.3

Maes.Inst

Select type of flow measurement

Volume ↑…

Volume measurement

Norm. Vol. ↑…

1

Standard volume flow measurement

Mass ↑...^

Mass flow measurement

1.1.4

Max. Flow

Set maximum flow rate

2

m

3

/h

Unit ↑...^

Select unit for volume flow

measurement

888888888

Upp.Limit

00600.0000 or other value
m

3

/h ↑…↑...↑...^

Enter value for the maximum volume

flow

Display Unit /

Display %Max Flow ↑...^

Display flow rate in units /

in % of maximum flow rate

3

m

3

/h norm

Unit ↑...^

Select unit for standard volume flow

measurement

00600.0000 or other value
m

3

/h norm ↑…↑...↑...^

Enter value for the maximum

standard volume flow rate

Display Unit /

Display %Max Flow ↑...^

Display flow rate in units /

in % of maximum flow rate

4

kg/h

Unit

Select unit for mass flow

measurement

00600.0000 or other value

kg/h ↑…↑...↑...^

Enter value for the maximum mass

flow rate

Display Unit /

Display %Max Flow ↑...^

Display flow rate in units /

in % of maximum flow rate

1.1.5

Min. Flow

001111111

00300.0000
m

3

/h ^

The minimum flow rate value is

factory-set.

1.1.6

Timeconst.

00002.0000

s ↑…↑...↑...^

Enter the time constant for the

measured value output in seconds

(0 – 20 s)

0: disabled

1 only with gas
2 available if Maes.Inst = Volume (see menu item 1.1.3)
3 available if Maes.Inst = Norm. Vol. (see menu item 1.1.3)
4 available if Maes.Inst = Mass (see menu item 1.1.3)