OPERATION

6

57

OPTISWIRL 4070

www.krohne.com

02/2013 - 4000150606 MA OPTISWIRL4070C R07 en

6.5.7 Menu item Setup (firmware version - steam)

Version Steam

Level

Designation

Selection / entry

Explanation

3.1

Set display

3.1.1

Error message

Display error

Yes ↑...

Shows error messages in measuring mode in plain text

alternating with the measured values

No ↑...^

Shows a flashing cursor in the top left corner of the

display to indicate that there are errors.

3.1.2

Cycle.Disp.

Display measured values

Yes ↑...

Cyclically display measured values in measuring mode

(6 s intervals)

No ↑...^

Do not display measured values cyclically

3.1.3

Code 1

Set security query 1 (menu)

Yes ↑...

Activate access code:

→→→↑↑↑^^^

No ↑...^

Deactivate access code

3.2

I/O settings

3.2.1

4-20mA off

Current output 4-20 mA and error current

4-20mA ↑...

Current output 4-20 mA

4-20/22E ↑...

Current output 4-20 mA or error current 22 mA

4-20/3.55E ↑...^

Current output 4-20 mA or error current 3.55 mA

3.2.2

Variable I

(available if DEVICE TYPE

= GROSS HEAT, see menu

item 5.4.1, service menu)

Set display variable for current output

Maes.Inst ↑...

Flow rate

Power ↑...^

Power

3.2.3

Power Unit

(available if DEVICE TYPE

= GROSS HEAT, see menu

item 5.4.1, service menu)

Set unit for heat output

kJ/h

Unit ↑...^

Select unit for measuring heat output

Disp. on /

Disp. off ↑...^

Display measured value/

Do not display measured value

3.2.4

FS power

(available if Variable I =

Power, see menu item

3.2.2)

End value for power measuring range

7000000.00

kJ/h ^

Power value at 20 mA current output

3.2.5

Function P

Pulse output

Yes ↑...

Activate pulse output

No ↑...^

Deactivate pulse output

3.2.6

Variable P

(available if DEVICE TYPE

= GROSS HEAT, see menu

item 5.4.1, service menu)

Set output variable for the pulse output

Total Flow ↑...

Total flow

Energy ↑...^

Energy

3.2.7

Totalizer

Totalizer

Tot. on ↑...

Start Totaliser

Tot. off ↑...^

Stop totalizer (value is held)

MA_OPTISWIRL4070C_R07_en_150606_PRT.book Page 57 Wednesday, February 13, 2013 2:47 PM