beautypg.com

Operation – KROHNE OPTISWIRL 4070 EN User Manual

Page 63

background image

OPERATION

6

63

OPTISWIRL 4070

www.krohne.com

02/2013 - 4000150606 MA OPTISWIRL4070C R07 en

3.4.2

Medium

(available if Fluid = Gas /

Wet Gas, see menu item

3.4.1)

Set process medium

Air ↑...

Air

Ammonia ↑...

Ammonia

Argon ↑...

Argon

etc. ↑...^

other gases not listed here

3.4.3

% Gas

(available if Fluid = Gas

Mix., see menu item 3.4.1)

Determine composition of gas mixture

050.000000

Air ↑…↑...↑...^

Select gas and enter percentage

100.00

Total % ^

Total percentage

3.4.4

%Rel.Hum

(available if Fluid = Wet

Gas, see menu item 3.4.1)

0000000.00

% Rel.Hum

↑…→↑...→↑...^

Determine relative humidity

3.4.6

FAD unit →

(available if Meter Type =

FAD meter, see menu

item 5.4.1, service

personnel only)

Determine unit for FAD

FAD m

3

/h

Unit ↑...^

Set unit for FAD

Disp. on /

Disp. off ↑...^

Display measured value /

Do not display measured value

3.4.7

Suct.Temp.

(available if Meter Type =

FAD meter, see menu

item 5.4.1, service

personnel only)

Enter temperature in suction area of compressor

°

C

Unit ↑...^

Select temperature unit

0000200.00
°

C ↑…↑...↑...^

Enter temperature value

3.4.8

Atm. Pressure

(available if Meter Type =

FAD meter, see menu

item 5.4.1, service

personnel only)

Atmospheric pressure

Pa

Unit ↑...^

Select pressure unit

00001.0000

Pa ↑…↑...↑...^

Enter pressure value

3.4.9

Fil. P. Drop.

(available if Meter Type =

FAD meter, see menu

item 5.4.1, service

personnel only)

Pressure drop via filter at compressor inlet

Pa

Unit ↑...^

Select pressure unit

00000.0000

Pa ↑…↑...↑...^

Enter pressure value

3.4.10

Inlet RH

(available if Meter Type =

FAD meter, see menu

item 5.4.1, service

personnel only)

0000060.00

% Rel.Hum

↑…→↑...→↑...^

Enter relative humidity in suction area of compressor

3.4.11

Actual Rpm

(available if Meter Type =

FAD meter, see menu

item 5.3.1, service

personnel only)

0001500.00

RPM ^

Current speed of compressor motor in revolutions per

minute

3.4.12

Rated Rpm.

(available if Meter Type =

FAD meter, see menu

item 5.4.1, service

personnel only)

0001500.00

RPM ^

Rated speed of compressor motor in revolutions per

minute

Version gas

Level

Designation

Selection / entry

Explanation

MA_OPTISWIRL4070C_R07_en_150606_PRT.book Page 63 Wednesday, February 13, 2013 2:47 PM