ELECTRICAL CONNECTIONS

4

35

OPTISWIRL 4070

www.krohne.com

02/2013 - 4000150606 MA OPTISWIRL4070C R07 en

4.3.1 Power supply

The required supply voltage can be calculated using the formula below:

U

ext.

= R

L

* 22mA + 14V

where
U

ext.

= the minimum supply voltage and

R

L

= the total measuring loop resistance is.

4.3.2 Totalizer / pulse output

The base units for the totalizer and the pulse output are m

m

m

m

3

33

3

for volume,

m

m

m

m

3

33

3

norm.

norm.

norm.

norm. for standard volume and kg

kg

kg

kg for mass.

The unit and the conversion factor can be changed in menu item 3.2.8 "Conf.Tot". User specific
units (User Def.) can also be entered but the conversion factor must always be entered based on
the base unit. For a sample calculation see chapter 6.2.5 "Change units".

The maximum frequency of the pulse output is 0.5 Hz.

INFORMATION!
The supply voltage has to be between 14 VDC and 36 VDC. This is based on the total resistance of
the measuring loop. To determine this, add up the resistances of each component in the
measuring loop (not including the measuring device).

INFORMATION!
The power supply has to be able to supply a minimum of 22 mA.

Figure 4-3: pulse output

1 f

max

≤ 0.5 Hz

2 closed
3 open
4 Pulse ≥ 250 ms