Index – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 43
2-31
IM04L41B01-65EN
1
2
3
4
Index
Viewing and Creating Setup Data
Setting the E-Mail Transmission
Transmit e-mail when creating a report.
Transmit e-mail when creating a report.
Select the recipient
Select the alarm
Transmit e-mail when storage medium error, etc.
are detected.
Transmit e-mail at specified time.
Transmit e-mail when alarm occurred/released.
Attach measured/computed data at that time 0
• SMTP server name
Set the SMTP server name (up to 64 alphanumeric characters) or the IP address of
the SMTP server.
• Port number
Set the port number to use in the range from 1 to 65535. The default value is [25].
• Recipient
Set the transmission destination of the e-mail message using up to 150 alphanumeric
characters. You can specify multiple addresses. To specify multiple addresses, delimit
the addresses using spaces.
• Sender
Set the e-mail address using up to 64 alphanumeric characters. If the address is not
set, the first address set in the recipient box is used as the sender’s address instead.
• Alarm
Transmits an e-mail message when alarm is active/released.
• Scheduled
Transmits an e-mail message when the specified time is reached.
• System
Transmits an e-mail message during recovery from a power failure, when memory end
is detected, or when an error related to the external storage medium and FTP client
occurs
• Report
Transmits an e-mail message when report is created (only on models with the optional
computation function (/M1)
• Subject, Header1, Header2
Subject: Set the subject of the e-mail message using up to 32 alphanumeric
characters.
Header1 and Header2: Set the string to be attached to the e-mail message using up t
64 alphanumeric characters.
2.6 Configuring the System Mode