Viewing and Creating Setup Data

Input Type and Span

Mode, Range/Type

Select from the list of choices from the pull-down menu.

Input Type

Mode

Range/Type

DC Voltage

VOLT

20 mV, 60 m V, 200 mV, 2 V, 6 V, 20 V, 50 V

Thermocouple

TC

TypeR, S, B, E, K, J, T, N, W, L, U

Resistance temperature detector RTD

Pt100, JPt100, Cu10*, Cu25*

ON/OFF input

DI

LEVEL (voltage level), CONT (Contact)

Measurement/Display OFF

SKIP

None

* /N1 option

Note

If SKIP is selected, settings such as Delta/Scale/Sqrt and Range/Type are discarded.

Span L, Span U

Sets the upper and lower limits (full scale) of the display.
When a value outside the range is entered or when the span L and span U values are set
to the same value, they are corrected when the data are checked.

Input value

Values within the

measurable range

Span L (0% on display)

Span U (100% on display)

Measured value

Difference Computation/Scaling/Square Root Computation

DELTA: Displays the difference between the input and the reference channel.

Note

Difference computation is performed between channels that have different [Mode] and

[Range/Type] settings. The decimal position of the computed result is set to that of the
channel computing the difference. If the number of digits to the right of the decimal of the
reference channel is greater than that of the channel computing the difference, the reference
value below the least significant digit of the channel computing difference is rounded
beforehand.

SCALE: Converts the input value to a value in the appropriate unit.
SQRT: Computes the square root of the input. The result is converted to a value in the
appropriate unit. This setting can be used only when the input mod is set to VOLT.

Input value

Measured value on the reference channel

DELTA

SCALE

SQRT

Input value

+

Span L

Scale L

Decimal position

Unit

Decimal position

Unit

Span U

Scale

conversion

Scale U

Input value

Span L

Span U

Span L

Scale L

Span U

Scale

conversion

Scale U

Measured value

Measured value

Measured value

Span L, Span U

Sets the appropriate upper and lower limits (see figures above).
When a value outside the range is entered or when the span L and span U values are set
to the same value, they are corrected when the data are checked.

2.3 Setting the Measurement Channels