Scan interval/memory/memory timeup, Scan interval/memory/memory timeup -20 – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 32
2-20
IM04L41B01-65EN
Remote (Option, /R1)
You can assign items to be controlled by the eight remote control terminals. This is
possible, if the remote function is available.
Scan Interval/Memory/Memory Timeup
Set these parameters when the data type is set to [EVENT & DISP] or [EVENT].
Click here (also selectable from [Setting] - [System Mode Setting]).
Check the channels you
wish to sample.
Select the
range.
Resets the
range selection.
Turn ON/OFF
at once.
A/D Integrate
100 ms can be selected only when the scan interval is set to [2 s].
Auto: The DXP will automatically switch between [60 Hz] or [50 Hz].
Scan Interval
The selectable scan intervals vary depending on the model as follows:
DX102P, DX104P, DX204P, DX208P: 125 ms and 250
DX106P, DX112P, DX210P, DX220P, DX230P: 1 s and 2 s
Memory Sample (Save Method of Measured/Computed Data)
• Data
When the data type is [EVENT], set [Event Data Sampling Rate] and [Data Length].
The selectable data length vary depending on the sampling rate. However, if the type
of process is set to [Batch] in the application settings of the system mode tab (see
page 2-22), the maximum selectable time is automatically entered and cannot be
selected.
• Sampling
Select the channels whose data is to be saved to the memory.
To collectively select or deselect a specified range, carry out the following procedure.
1. Specify the range by dragging the mouse over the desired range on the column (if
you do not carry out this step, all channels are specified). You can reset the range
by pressing the Initialize button.
2. The selected/deselected condition of the specified range of channels switch each
time the ON/OFF at once button is clicked.
2.6 Configuring the System Mode